MULTICAL® 62 • Water meter
7 Information Codes “INFO”
MULTICAL® 62 constantly monitors a number of important functions. If there is a serious error in
measuring system or installation, a lashing “INFO” will appear in the display until the error has
been corrected. The “INFO” ield lashes as long as the error exists no matter which reading you
choose. The “INFO” ield automatically disappears when the reason for the error has been removed.
When the irst permanent information code appears it is saved in the EEPROM together with the
date and the volume registers at the time the error occurred.
Furthermore, the info code is saved in the hourly logger (if a top module with hourly logger is
mounted), the daily logger, the monthly logger and the yearly logger for diagnosis purposes.
Info code types
Info
Description
Response time
0
No irregularities
-
1
Supply voltage has been interrupted
-
16
Flow sensor V1, communication error
After reset (e.g. cover off and on) as well
as automatically after max. 24 hours (at
00:00)
64
Leak in water installation.
The Water has
not
been stagnant in the
meter for
minimum
one continuous hour
during the latest 24 hours.
This can be a sign of a leaky faucet or toilet
cistern.
24 hours
2048 Flow meter V1, wrong pulse igure
After reset (e.g. cover off and on) as well
as automatically after max. 24 hours (at
00:00)
4096 Flow meter V1, signal too weak (air)
16384 Flow meter V1, wrong low direction
If several info codes appear at a time, the sum of the info codes is displayed.
Example: E2064 = E16 + E2048.
7.1 Transport mode
The meter leaves the factory in transport mode, i.e. the info codes are active in the display only, not
in the data logger. This prevents “infoevent” from counting during transportation and non-relevant
data from being saved in the info logger. The irst time the meter totalizes the volume register after
the installation, the info codes automatically become active.