
TECHNICAL DESCRIPTION Wired M-Bus • Water Meters flowIQ® 2101
/
3100
26
Kamstrup A/S · Technical Description · 55121944_A1_GB_08.2016
8.3
Data header in RSP_UD
Data
Value
Type Description
ID-NO
Xxh
A
M-Bus ID number
∗
10
1
/ M-Bus ID number
∗
10
0
ID-NO
Xxh
A
M-Bus ID number
∗
10
3
/ M-Bus ID number
∗
10
2
ID-NO
Xxh
A
M-Bus ID number
∗
10
5
/ M-Bus ID number
∗
10
4
ID-NO
Xxh
A
M-Bus ID number
∗
10
7
/ M-Bus ID number
∗
10
6
MANUFACTURER
00101101
C
Manufacturer Id 2D [ascii ‘K’ - 64]
∗
32
∗
32+[ascii ‘A’ – 64]
∗
32+
MANUFACTURER
00101100
C
Manufacturer Id 2C [ascii ‘M’ - 64] ISO 60870 standard
VERSION ID
1Fh
1Dh
C
M-Bus version ID for flowIQ2101
M-Bus version ID for flowIQ3100
DEVICE TYPE ID
Xxh
C
06h = Volume warm
16h = Volume cold
ACCESS NO
Xxh
C
Counts 1 up for each data transmission to M-Bus Master
STATUS
Xxh
C
00h = No Info code
04h = Power Low on battery
10h = Temporary error
14h = Power Low and Temporary error at the same time
ENCRYPTION
CONFIGURATION
00h
C
Encryption not used in Wired M-Bus
ENCRYPTION
CONFIGURATION
00h
C
Encryption not used in Wired M-Bus