Venkon XL
Assembly, installation and operating instructions
62
Parameter
Function
Standard
Min.
Max.
Unit
Venkon XL*
P123
Maximum valve running time
150
0
255
sec
150
P124
Minimum P + I output variation for valve movement (0 to
10)
5
0
100
%
5
P125
reserved
-
-
-
-
-
P126
Operating weeks
0
0
255
week
0
P127
Information on operating weeks reached (filter message)
0
52
255
week
0
P128
Reset operating week counter
0
0
1
-
0
P129
Fan speed limiter activation in certain operating modes
0
0
1
-
0
P130
Absolute fan speed increase via contact
2
0
5
-
2
P131
External ventilation, delay time
0
0
255
min.
0
P132
Operating level, master password
22
0
255
-
22
P133
Hysteresis for outside temperature to switch between heat-
ing/fan mode
0
0
255
K/10
0
P134
Threshold for outside temperature to switch between heat-
ing/fan mode
0
0
50
°C
0
P135
Activate virtual sensor
0
0
1
-
0
P136
Activate external ventilation
0
0
2
-
0
Tab. 13: Parameter key, SAP no. 9001373, dated 10.07.2020