Description of wiring
Factory-fitted actuators are wired to the terminal. The appropriate terminals are available for valve drives on site.
The speed of EC fans used is continuously variably controlled by a 0 – 10 V DC signal. The “intelligent” motor electronics
detects any possible motor fault and automatically switches off the fan.
Fig. 18: Junction box of Venkon XL
Note these points in the following wiring diagrams for Venkon XL with electromechanical control:
Comply with the details on cable types and cabling with due consideration of VDE 0100.
Without *: NYM-J. The requisite number of wires, including PE conductor, is stated on the cable. Cross-sections are not
stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8 mm. Lay separately from high-voltage lines.
If other types of cables are used, they must be at least equivalent.
The terminals on the unit are suitable for a maximum wire cross-section of 2.5 mm².
We recommend type F when using RCCBs. Refer to the provisions of DIN VDE 0100 Parts 400 and 500 when configuring
the rated fault current.
Note the