Venkon XL
Assembly, installation and operating instructions
33
6.5.5 Connection, on-site pipework
6.5.6 Condensation connection
6.5.6.1
Condensation drain with natural gradient
A condensate drain provided by the customer must be connected to a condensate drain socket of the Venkon (size of drain
15 mm / 0.6 inch) and fastened accordingly. To ensure condensation drainage from the base unit, the slope must be at least 1
% without restriction and without rising pipe sections (according to DIN EN 12056; old: DIN 1986-100). Ensure that the base
unit is mounted horizontally. Should this not be possible, only install the unit with a slight slope in the condensate drain dir-
ection, otherwise condensate will remain in the main condensate tray. When connecting the condensate drain to the sewage
system, the valid regulations must be observed, such as the use of a ball siphon. The siphon must be protected from drying
out. Due to the suction effect of the fan on the condensate drain socket, it could otherwise lead to odor nuisance. Depending
on the pipe material used by the customer for the condensate drainage, vapor diffusion-tight insulation may be required.
Should a natural slope not be possible on site, a condensate pump (optional accessory) is required. Its purpose is to transport
the condensate to collection or discharge facilities located at a higher level.
When ordered, the condensate pump with float switch is mounted to the unit by the manufacturer.