Venkon XL
Assembly, installation and operating instructions
46
7.3
KaControl (*C1)
7.3.1 KaController installation
Fig. 19: Installation of flush-mounted back box
Fig. 20: KaController terminals
Electrical connection
Connect the KaController to the nearest KaControl unit in
line with the wiring diagram. The maximum bus length
between the KaController and the KaControl master unit
is 30 m.
The respective KaControl automatically becomes the
master unit in the control circuit when a KaController is
connected to it.
Fig. 21: DIP switch setting on KaController
DIP switch setting
The DIP switches on the rear of the KaController should be
set according to the illustration:
DIP switch 1: ON
DIP switch 2: OFF
Содержание Venkon XL
Страница 2: ......