Ultra Allround
Assembly, installation and operating instructions
50
10.3 Maintenance work
10.3.1 Visual checks
Clean the heat exchanger.
Check the heat exchanger for soiling and carefully vacuum if necessary. Avoid damage to the pipework and fins.
10.3.2 Clean the inside of the unit
Check all elements that come into contact with air (internal surfaces of the unit, outlet elements etc.) for dirt or deposits dur-
ing maintenance and use a commercially available product to remove.
DANGER!
Risk of injury from burning
The electronics housing of the EC fan reaches high temperatures. Avoid direct contact!
IMPORTANT NOTE!
Do not use aggressive cleaning agents!
Aggressive cleaning agents that can damage the paintwork must not be used on the EC fan. Water must not
enter the inside of the motor or the electronics (through direct contact with seals or motor openings, for ex-
ample), respect the protection rating (IP). The condensation drain holes (if present), positioned to suit the in-
stallation situation, must be checked for clearance. Run the EC fan for at least 1 hour at 80 to 100% of max-
imum speed before cleaning to prevent moisture accumulating in the motor! Run the EC fan for a minimum
of 2 hours at 80 to 100% of maximum speed after the cleaning process!
Содержание Ultra Allround
Страница 2: ......