Ultra Allround
Assembly, installation and operating instructions
23
7
Electrical connection
7.1
Maximum electrical rating values
Electromechanical version
Item no.
Rated
voltage [V]
Power fre-
quency [Hz]
Active
power [kW]
Rated cur-
rent [A]
Leakage cur-
rent [mA]
Maximum
backup fuse
[A]
IP protec-
tion class
Protection
class
354xxxx7xx5
800
230
50
268
1.2
<3.5
C16
IP20
I
354xxxx7xx5
8C1
230
50
268
1.2
<3.5
C16
IP20
I
Tab. 5: Electrical specifications Ultra
7.2
Electromechanical control
7.2.1 Connection (*00)
Circuit description
All units need a 230 V AC power supply
A lockable repair switch is always fitted to the electrical housing, and connected.
Factory-fitted actuators are wired to the terminals. The appropriate terminals are available for valve actuators.
Only 24 V DC valve actuators (Open/Closed or continuous) can be connected.
The speed of the EC fans is controlled by a 0-10 V DC signal from the KaControl. The “intelligent” motor electronics de-
tects any possible motor malfunction and automatically switches off the fan.
The cooling valve (Y1) is actively closed in the event of a condensate alarm.
A motor malfunction signal is available to the potential-free contact f.e1/f.e2 (30 V DC / 2 A).
A condensate alarm is available to the potential-free contact c.a1/c.a2 (30 V DC / 2 A).
The control board has various LEDs for the visual display.
It also features a micro-fuse.
Fig. 8: Open the electrical box.