Ultra Allround
Assembly, installation and operating instructions
26
Section of the printed circuit board
Description
Terminal block X7 (fan / condensate pump power supply connection):
230 V AC / 50 Hz
Fan and condensate pump
Terminal block X10 (output voltage):
Output voltage 230 V AC / 50 Hz
Possible indication:
Repair switch activated / deactivated
Fuse or electrical unit failure
Visual display:
LED 1 (red) = condensate pump fault
Cp = condensate pump / dpm = dew point measure / humidity
LED 2 (yellow) = cooling switch-over active
Fuse F1:
Fuse 4 A slow-acting
230 V AC
Dimensions: 5 x 20 mm
Jumper J1 (fan speed limit with wet cooling)
Jumper inserted: fan speed reduction to approx. 7.5 V
No jumper: no fan speed reduction (10 V)
Repair switch
A lockable repair switch is always fitted and connected to the electrical
housing
.