Katherm HK
Assembly, installation and operating instructions
76
Parameter
Function
Standard
Min.
Max.
Unit
Katherm HK
9
Katherm HK
E
10
P069
Network address
1
0
207
-
1
1
P070
Dependence of the hydronic algorithms (on slaves)
0
0
7
-
0
0
P071
Serial address of slave 1
0
0
207
-
0
0
P072
Serial address of slave 2
0
0
207
-
0
0
P073
Serial address of slave 3
0
0
207
-
0
0
P074
Serial address of slave 4
0
0
207
-
0
0
P075
Serial address of slave 5
0
0
207
-
0
0
P076
Serial address of slave 6
0
0
207
-
0
0
P077
Serial address of slave 7
0
0
207
-
0
0
P078
Serial address of slave 8
0
0
207
-
0
0
P079
Serial address of slave 9
0
0
207
-
0
0
P080
Serial address of slave 10
0
0
207
-
0
0
P081
Dependence of the hydronic algorithms, slave 1
0
0
7
-
0
10
P082
Dependence of the hydronic algorithms, slave 2
0
0
7
-
0
18
P083
Dependence of the hydronic algorithms, slave 3
0
0
7
-
0
0
P084
Dependence of the hydronic algorithms, slave 4
0
0
7
-
0
0
P085
Dependence of the hydronic algorithms, slave 5
0
0
7
-
0
0
P086
Dependence of the hydronic algorithms, slave 6
0
0
7
-
0
0
P087
Dependence of the hydronic algorithms, slave 7
0
0
7
-
0
0
P088
Dependence of the hydronic algorithms, slave 8
0
0
7
-
0
0
P089
Dependence of the hydronic algorithms, slave 9
0
0
7
-
0
0
P090
Dependence of the hydronic algorithms, slave 10
0
0
7
-
0
0
P091
Load default values
0
0
255
-
0
0
P092
Password management
0
0
255
-
0
0
P093
Type of pre-comfort (room occupancy)
0
0
3
-
0
0
P094
Pre-comfort timer
60
1
255
min
60
60
P095
Disable DIP switch settings
0
0
1
-
0
0
P096
Digital outputs continuously activated
0
0
1
-
0
0
P097
Read off DIP switch
-
0
63
-
-
-
P098
Activation 0..10 V: valve switch on limit
30
0
100
V/10
40
40
P099
Activation 0..10 V: min. switch on limit for fan speed
40
0
100
V/10
40
40
P100
Activation 0..10 V: max. switch on limit for fan
speed
90
0
100
V/10
90
90
P101
Valve activation by pulse width modulation of P-
band in heating mode
15
0
100
K/10
15
15
P102
Valve activation by pulse width modulation of P-
band in cooling mode
15
0
100
K/10
15
15
P103
Valve activation by pulse width modulation of reset
time of PI controller
0
0
20
min
0
0
P104
Minimum ON time with PWM valve activation
3
0
20
min
3
3
P105
Compensation: max. negative delta setpoint
50
0
150
K/10
50
50
P106
Compensation: max. positive delta setpoint
50
0
150
K/10
50
50
P107
Duration of valve open to check water temperature
5
0
255
min
5
5
P108
Duration of valve closed
240
35
255
min
240
240
P109
Dead zone PI control for 3-way valve
10
0
100
K/10
10
10
P110
Hysteresis to switch between heating / fan mode
0
0
20
°C
0
0
P111
Threshold to switch between heating / fan mode
0
0
50
°C
0
0
Содержание Katherm HK
Страница 2: ......
Страница 16: ...Katherm HK Assembly installation and operating instructions 16 6 2 1 Installation steps ...
Страница 18: ...Katherm HK Assembly installation and operating instructions 18 by others Expansion joint on site ...
Страница 19: ...Katherm HK Assembly installation and operating instructions 19 ...
Страница 79: ...Katherm HK Assembly installation and operating instructions 79 13 Certificates ...
Страница 83: ......