Katherm HK
Assembly, installation and operating instructions
74
12
List of KaControl parameters
12.1 Katherm HK/ HK E parameter list
Parameter
Function
Standard
Min.
Max.
Unit
Katherm HK
9
Katherm HK
E
10
P000
Software version
24
0
255
-
24
24
P001
Base setpoint for setpoint input ± 3K
22
8
32
°C
22
22
P002
Switch-on and switch-off hysteresis for valves
3
0
255
K/10
1
1
P003
Neutral zone in a 4-pipe system (only in automatic
mode)
3
0
255
K/10
20
20
P004
Cooling without fan assistance (natural convection)
0
0
255
K/10
0
0
P005
Heating without fan assistance (natural convection)
5
0
255
K/10
0
0
P006
Fan On/Off hysteresis (only in ventilation mode)
5
0
255
K/10
5
5
P007
P-band, heating
20
0
100
K/10
25
25
P008
P-band, cooling
20
0
100
K/10
25
25
P009
Offset to the base setpoint for setpoint input ± 3K
3
0
10
C
3
3
P010
Contact sensor: limit value temperature to activate
fan stages 1 and 2 in heating mode
26
0
255
°C
26
26
P011
Contact sensor: limit value temperature to activate
fan stages 3 and 4 in heating mode
28
0
255
°C
28
28
P012
Contact sensor: limit value temperature to activate
fan stage 5 in heating mode
30
0
255
°C
30
30
P013
Contact sensor: hysteresis for limit temperatures
P010, P011, P012, P014
10
0
255
K/10
10
10
P014
Contact sensor: limit value temperature to activate
fan stages in cooling mode
18
0
255
°C
18
18
P015
Function of input AI1
0
0
19
-
0
0
P016
Function of input AI2
0
0
19
-
0
13
P017
Function of input AI3
0
0
9
-
0
0
P018
Temperature increase of cooling setpoint in Eco
mode
30
0
255
K/10
30
30
P019
Temperature decrease of heating setpoint in Eco
mode
30
0
255
K/10
30
30
P020
ADC limit coefficient
6
0
15
-
6
6
P021
ADC average coefficient
6
0
15
-
6
6
P022
Activation / deactivation of sun symbol in Comfort
mode
0
0
1
-
0
0
P023
Difference for compensation in cooling
0
-99
127
K/10
0
0
P024
Coefficient for compensation in cooling
0
-20
20
1/10
0
0
P025
Difference for compensation in heating
0
-99
127
K/10
0
0
P026
Coefficient for compensation in heating
0
-20
20
1/10
0
0
P027
Fan setting: maximum run-time for manual fan
mode
0
0
255
min
0
0
P028
Rinsing function: fan stage during the purging func-
tion
2
1
5
-
2
2
P029
Activation of continuous fan mode
0
0
1
-
0
0
9
Parameter key Katherm HK, SAP no. 9001380, date 10.07.2020
10
Parameter key Katherm HK E, SAP no. 9001631, date 29.10.2021
Содержание Katherm HK
Страница 2: ......
Страница 16: ...Katherm HK Assembly installation and operating instructions 16 6 2 1 Installation steps ...
Страница 18: ...Katherm HK Assembly installation and operating instructions 18 by others Expansion joint on site ...
Страница 19: ...Katherm HK Assembly installation and operating instructions 19 ...
Страница 79: ...Katherm HK Assembly installation and operating instructions 79 13 Certificates ...
Страница 83: ......