Fault
Possible cause
Remedy
Unit too loud
Speed too high.
Set a lower speed, if possible.
Air inlet/outlet opening is obstructed.
Free air ducts.
Filter dirty.
Replace filter.
Rotating parts unbalanced
Clean and/or replace impeller. Please make sure
that no balancing clips are removed during
cleaning.
Fan dirty.
Clean dirt from fan.
Heat exchanger dirty.
Clean dirt from Heat exchanger.
11.2 KaControl faults
Code
Alarms
Priority
A11
Faulty control sensor.
1
A12
Motor fault.
2
A13
Room frost protection.
3
A14
Condensation alarm.
4
A15
General alarm.
5
A16
Sensor AI1, AI2 or AI3 faulty.
6
A17
Unit frost protection.
7
A18
EEPROM error.
8
A19
Offline slave in the CAN bus network.
9
Tab. 18: KaControl unit alarms
Code
Alarms
tAL1
Temperature sensor in the KaController faulty.
tAL3
Real-time clock in the KaController faulty.
tAL4
EEPROM in the KaController faulty.
Cn
Communication fault with the external control.
Tab. 19: KaController alarms
IMPORTANT NOTE!
Important note!
More information on control settings can be found in the separate KaControl SmartBoard user manual.
11.3 Start-up after rectification of fault
After correction of the fault, carry out the following steps to re-start:
1. Make sure that all maintenance covers and access openings are sealed.
2. Switch off the unit.
3. Acknowledge fault on controller, if necessary.
Содержание Katherm HK
Страница 2: ......
Страница 16: ...Katherm HK Assembly installation and operating instructions 16 6 2 1 Installation steps ...
Страница 18: ...Katherm HK Assembly installation and operating instructions 18 by others Expansion joint on site ...
Страница 19: ...Katherm HK Assembly installation and operating instructions 19 ...
Страница 79: ...Katherm HK Assembly installation and operating instructions 79 13 Certificates ...
Страница 83: ......