Katherm HK
Assembly, installation and operating instructions
34
Connecting the condensate pump
Push the suction hose as far as it will go and fix in place with a cable tie to prevent the pump from running dry.
Cable tie
Suction hose
Suction connection
Condensation pump
Fig. 5: Fixing the suction hose
Supply power and wire alarm contact (separate cable with plug) as per the wiring diagram.
Connect the hose to the condensate drain (separate). Direction of flow: refer to the arrow on the side of the housing
Operating voltage [V]
120
230
Mains frequency [Hz]
60
50/60
Electrical supply [A / W]
0.29 / 15
0.17 / 16
Max. delivery volume 0 m / ft per hour [l / US
gal]
12 / 3.2
12 / 3.2
Max. delivery height [m / ft]
10 / 33
10 / 33
Noise level at a distance of 1 m / 3.3 ft
25
21
Operating mode
S1: Continuous operation
S1: Continuous operation
Protection class
II
II
Maximum output [kW / Btu/h]
9 / 30000
9 /30000
Max. water temperature [°C / °F]
40 / 104
40 / 104
Inner diameter of drain hose [mm / "]
6 / 1/4
6 / 1/4
Suction height [m / ft]
1 / 3.3
1 / 3.3
Tab. 4: Technical data for condensate pump
Potential-free alarm contacts, 3 A, normally closing, sound power for inductive loads 5 A at 230 V
Hall effect semiconductor-based level sensors, excellent safety
Integrated thermal cut-out
Fully sealed
Fuse 1 A (by others)
* Maximum recommended operating delivery height
Содержание Katherm HK
Страница 2: ......
Страница 16: ...Katherm HK Assembly installation and operating instructions 16 6 2 1 Installation steps ...
Страница 18: ...Katherm HK Assembly installation and operating instructions 18 by others Expansion joint on site ...
Страница 19: ...Katherm HK Assembly installation and operating instructions 19 ...
Страница 79: ...Katherm HK Assembly installation and operating instructions 79 13 Certificates ...
Страница 83: ......