64
3.26
KaDeck
Versatile air conditioning for offices and administration buildings
Installation and operating instructions
Parameter P44
Parameter P44 is used to set the function of the digital input DI2 when DIP
switch no. 4 = OFF.
The digital input DI1 is predominantly used to execute specific functions. If
the use of the digital input DI2 is needed, then the following settings have
to be made:
1. Set DIP switch no. 4 to OFF.
2. Configuration of the digital input DI2 using parameter settings P44.
6.17.3 DI2 function
Function
Standar
d
Min.
Max.
Unit
P44
Function DI2
0 = No function
1 = ON/OFF
(contact open
ON)
2 = Heating/cooling changeover (contact open
heating)
3 = Eco/day mode
(contact open
Day)
4 = No function
(contact open
no function)
5 = Condensation alarm
(contact open
no condensation)
6 = General alarm
(contact open
no alarm
7 = Ext. frost protection monitor (contact open
no frost)
8 = ON/OFF
(contact closed
ON)
9 = Heating/cooling changeover (contact closed
heating)
10 = Eco/Day mode
(contact closed
day)
11 = No function
(contact closed
no function)
12 = Condensation alarm
(contact closed
no condensation)
13 = General alarm
(contact closed
no alarm)
14 = Ext. frost protection monitor (contact closed
no frost)
15 = Special mode
(contact open
special mode active)
16 = Special mode
(contact closed
special mode active)
17 = Fan stage increase
(contact open
no fan stage increased)
18 = Fan stage increase
(contact closed
no fan stage increase)
19 = Heating/cooling changeover (contact open
heating)
20 = Heating/cooling changeover (contact closed
heating)
21 = Cooling/heating changeover (contact open
heating)
21 = Cooling/heating changeover (contact closed
cooling)
0
0
22
If DIP switch no. 4 is set to ON, digital input DI2 changes over from
heating to cooling in a 2-pipe system.
On the KaDeck, the digital input DI2 is connected to GND via a
factory-inserted electrical jumper. The KaDeck is therefore pre-set as a
cooling unit.