KaDeck
Versatile air conditioning for offices and administration buildings
Installation and operating instructions
DIP switch no. 1
DIP switch no. 1 must be set to ON to actuate a KaControl by means of
0…10 V signals within a building management system provided by others.
The parameter settings required are described in section 10.3.17.
Factory setting: DIP1 = OFF
DIP switch no. 2
It is essential that DIP switch no. 2 is set to OFF.
Factory setting: DIP2 = OFF
DIP switch no. 3
A temperature sensor can be connected to provide interim frost protection.
In this case, DIP switch no. 3 has to be set to ON.
Factory setting: DIP3 = OFF
DIP switch no. 4
Cooling/heating changeover is set as standard using the KaController.
Alternatively, cooling/heating changeover can also be performed by an
external switch contact. In this case, DIP switch no. 4 has to be set to ON.
The KaDeck is designed as a 2-pipe unit and the DIP switch is set to ON.
Factory setting: DIP4 = ON
DIP switch no. 5
It is essential that DIP switch no. 5 is set to OFF.
Factory setting: DIP5 = OFF
DIP switch no. 6
There is an option of using the internal sensor in the KaController or an
external room temperature sensor for temperature control.
DIP switch no. 6 = OFF
Room temperature control on an internal
sensor or external room temperature sensor.
DIP switch no. 6 = ON
Room temperature control on the internal
sensor of the KaController
Factory setting: DIP6 = OFF