15
KaDeck
3.26
Versatile air conditioning for offices and administration buildings
Installation and operating instructions
One-sided discharge
Dry cooling model
1)
Wet cooling model
2)
Speed range
Maximum
Medium
5)
Minimum Maximum
Medium
5)
Minimum
Control voltage
[V]
10
8
6
4
2
10
8
6
4
2
Air volume
V[m³/h]
337
278
221
163
106
196
157
119
81
42
Power consumption
P[W]
20
17
9
5
4
20
17
9
5
4
Speed
n [rpm]
1100
925
750
575
400
1100
925
750
575
400
Sound pressure level
4)
L
WA
[dB(A)]
37
33
29
25
20
35
33
27
23
<20
Sound power level
L
PA
[dB(A)]
45
41
37
33
28
43
41
35
31
<28
Cooling mode
Cooling output
Q
k
[W]
999
837
672
498
314
1609
1392
1157
891
588
Outlet air
temperature
t
L2
[°C]
17.6
17.3
17.1
16.8
16.5
12.4
11.9
11.2
10.5
9.4
Water volume
V[l / h]
430
360
289
214
135
277
239
199
153
101
Pressure loss
dP [kPa]
29
21.2
14.4
8.5
3.8
8
7
5
3
1.2
Heating mode
3)
Heat output
Q
H
[W]
4176
3495
2807
2077
1308
2936
2493
2024
1515
961
Water volume
V[l / h]
223
188
152
113
72
154
132
107
81
52
Pressure loss
dP[kPa]
7.7
5.7
3.9
2.3
2.31
3
2
1
1
1
One-sided discharge
Dry cooling model
1)
Wet cooling model
2)
Speed range
Maximum
Medium
5)
Minimum Maximum
Medium
5)
Minimum
Control voltage
[V]
10
8
6
4
2
10
8
6
4
2
Air volume
V[m³/h]
635
525
418
308
199
369
297
225
152
79
Power consumption
P[W]
30
27
14
7
5
30
27
14
7
5
Speed
n [rpm]
1100
925
750
575
400
1100
925
750
575
400
Sound pressure level
4)
L
WA
[dB(A)]
40
36
32
28
23
38
35
30
26
21
Sound power level
L
PA
[dB(A)]
48
44
40
36
31
46
43
38
34
29
Cooling mode
Cooling output
Q
k
[W]
1718
1465
1203
921
607
3114
2650
2153
1598
979
Outlet air
temperature
t
L2
[°C]
18.6
18.3
17.9
17.5
17
11.2
10.6
10
9.3
8.4
Water volume
V[l / h]
738
630
517
396
261
535
456
370
275
168
Pressure loss
dP [kPa]
75.3
56.9
40.2
25.2
12.1
55
41
29
17
7
Heating mode
3)
Heat output
Q
H
[W]
7185
6124
5028
3850
2533
5339
4465
3554
2578
1530
Water volume
V[l / h]
379
324
268
206
137
286
240
192
140
84
Pressure loss
dP[kPa]
19.6
14.9
10.6
6.7
3.3
15
10
7
4
2
1) with LPHW 16 / 18 °C, t
L1
= 27 °C
2) with CHW 7 / 12 °C and t
L1
= 27 °C, 48% relative humidity
3) with LPHW 75 / 65 °C, t
L1
= 20°C
4) The sound pressure levels were calculated with an assumed room insulation of 8 dB(A).
This corresponds to a distance of 2 m, a room volume of 100 m³ and a reverberation time of 0.5 s (in accordance with VDI 2081)
5) Recommended speed range of fans for optimum energy efficiency and comfort
3.5 Operating data
Version: one-sided discharge for under-ceiling installation
Version: two-sided discharge for under-ceiling installation