3. Reverse the Inlet Supplies (optional)
The inlet connections are indicated on the inlet ports of the
thermostatic valve assembly. Left is HOT and right is COLD. If this
configuration is not suitable for your installation, the cartridge may
be rotated 180° to reverse the hot and cold inlet ports.
NOTE:
DO NOT pull the removal clip from the cartridge assembly
at any time during this procedure. The retaining clip helps hold the
temperature limit stop and detent components in place and reduces
or eliminates the need for temperature adjustments.
With the valve already installed and pressurized:
Turn both integral supply stops until they contact the stop
bracket.
Turn the volume control valve stem (not shown) fully clockwise
to release the pressure.
Slowly loosen the head nut, turning it counterclockwise. This will
begin to draw the cartridge out of the valve body.
NOTE:
Some water may be released. Use a bucket and towels to
contain the water.
Pull the head nut with the cartridge out of the valve body.
NOTE:
Two seals may fall out when the cartridge is removed. Set
the seals aside.
Rotate the cartridge 180°.
Rotate 180˚.
Head Nut
Integral
Supply Stops
Valve Stem
Adapter
Seals
Cartridge
Tab
Rotate the Cartridge
Inlet Connections
Cartridge
Slot
Inlet
Port
Inlet
Port
On
Off
Stop Bracket
Body Fully
Threaded
Body Fully
Threaded
Lift service stop
tool to reveal
check valve/filter
screen body.