Drainage pipe installation
Installation
69
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less than two hangers.
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
Содержание SUPER DC INVERTER SERIES
Страница 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Страница 2: ...ii General Information ...
Страница 4: ......
Страница 16: ...Dimensions LFIS B 1211 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275 ...
Страница 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Страница 30: ...Duct Type LFIS B 1211 26 Indoor Units 4 Wiring Diagrams KTB 18HWFN1 QRC4 KTB 24HWDN1 QRC4 KTB 36HWFN1 QRC4 ...
Страница 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Страница 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Страница 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Страница 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Страница 79: ...LFIS B 1211 Engineering of insulation Installation 75 cause leakage to damage the house decoration ...
Страница 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...