LFIS-B-1211
Troubleshooting
Electrical Control System
89
2.2 Indoor unit malfunction
NO.
Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Display(digital
tube)
1
Communication malfunction between indoor
and outdoor units.
X
☆
X
X
E1
2
Open or short circuit of T1 temperature
sensor
☆
X
X
X
E2
3
Open or short circuit of T2 temperature
sensor
☆
X
X
X
E3
4
Open or short circuit of T2B temperature
sensor
☆
X
X
X
E4
5
Full-water malfunction
X
X
X
☆
EE
6
Indoor EEPROM malfunction
◎
X
X
X
E7
7
Outdoor unit malfunction
X
X
X
◎
Ed
8
Indoor fan speed is out of control
☆
☆
X
X
E8
9
Communication malfunction between main
PCB and up-down panel PCB
☆
☆
☆
X
F0
10
Up-down panel malfunction
☆
☆
X
☆
F1
11
Up-down panel is not closed
☆
☆
X
O
F2
12
Communication malfunction between master
unit and slave unit
X
☆
X
☆
F3
13
Other malfunction of master unit or slave unit
X
☆
☆
X
F4
O (on) X(off)
☆
(flash at 5Hz)
◎
(flash at 0.5Hz)
2.3 Outdoor unit malfunction
Display
Malfunction or Protection
E0
Outdoor EEPROM malfunction
E2
Indoor / outdoor units communication error
E3
Communication malfunction between IPM board and outdoor main board
E4
Open or short circuit of T3 or T4 temperature sensor
E5
Voltage protection of compressor
E6
PFC module protection (For 30K-48K)
E8
Outdoor fan speed has been out of control
P0
Top temperature protection of compressor
P1
High pressure protection
P2
Low pressure protection
P3
Current protection of compressor
P4
Discharge temperature protection of compressor
P5
High temperature protection of condenser
P6
IPM module protection
P7
High temperature protection of evaporator
Содержание SUPER DC INVERTER SERIES
Страница 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Страница 2: ...ii General Information ...
Страница 4: ......
Страница 16: ...Dimensions LFIS B 1211 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275 ...
Страница 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Страница 30: ...Duct Type LFIS B 1211 26 Indoor Units 4 Wiring Diagrams KTB 18HWFN1 QRC4 KTB 24HWDN1 QRC4 KTB 36HWFN1 QRC4 ...
Страница 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Страница 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Страница 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Страница 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Страница 79: ...LFIS B 1211 Engineering of insulation Installation 75 cause leakage to damage the house decoration ...
Страница 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...