Troubleshooting
LFIS-B-1211
102
Electrical Control System
2.4.4.6. E4 malfunction
Judge 1: Outdoor condenser temp. sensor (T3) is malfunction
E4 display
No
No
Replace condenser temp. sensor(T3)
Check whether the wiring of the
condenser temp. sensor(T3) is
broken off
Check whether the resistance of
condenser temp. sensorT3) is
wrong refer to the
Appendix
1
Yes
Connect the wiring well
Yes
Judge 2: Outdoor ambient temp. sensor (T4) is malfunction
No
Replace outdoor ambient
temperature sensor (T4)
Check whether the wiring of the
outdoor ambient temperature
sensor (T4) is broken off
Check whether the resistance of
outdoor ambient temperature
sensor (T4) is wrong refer to the
Appendix
1
Yes
Connect the wiring well
Yes
No
Replace outdoor main PCB
Содержание SUPER DC INVERTER SERIES
Страница 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Страница 2: ...ii General Information ...
Страница 4: ......
Страница 16: ...Dimensions LFIS B 1211 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275 ...
Страница 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Страница 30: ...Duct Type LFIS B 1211 26 Indoor Units 4 Wiring Diagrams KTB 18HWFN1 QRC4 KTB 24HWDN1 QRC4 KTB 36HWFN1 QRC4 ...
Страница 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Страница 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Страница 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Страница 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Страница 79: ...LFIS B 1211 Engineering of insulation Installation 75 cause leakage to damage the house decoration ...
Страница 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...