LFIS-B-1211
Troubleshooting
Electrical Control System
101
2.4.4.5. E3 malfunction
Communication malfunction between
IPM board and outdoor main board
Is there at least one LED in
the IPM board light?
Check the signal wire between
the IPM module and the main
board, is it connected good?
Reconnect and retry. Is
error still display?
Replace IPM board, and
then check whether the
system can run normally
Replace the electric control
box
No
No
No
No
Yes
Trouble is solved
No
Yes
Replace outdoor main
board, and then check
whether the system can run
normally
No
Yes
Yes
E3 display
Содержание SUPER DC INVERTER SERIES
Страница 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Страница 2: ...ii General Information ...
Страница 4: ......
Страница 16: ...Dimensions LFIS B 1211 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275 ...
Страница 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Страница 30: ...Duct Type LFIS B 1211 26 Indoor Units 4 Wiring Diagrams KTB 18HWFN1 QRC4 KTB 24HWDN1 QRC4 KTB 36HWFN1 QRC4 ...
Страница 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Страница 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Страница 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Страница 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Страница 79: ...LFIS B 1211 Engineering of insulation Installation 75 cause leakage to damage the house decoration ...
Страница 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...