background image

PRELIMINARY 

Subject 

to 

Revision

KCF 25, 50

4

The waste water destined for indirect discharge must not exceed 

a hydrocarbon concentration of 20 ppm.
Please note that the national legal limit values for indirect dis-

charge may vary regionally. 

Please check if your KCF type corresponds to 

these instructions. 

Application:

The KCF unit is designed for the treatment of demulsifiable 

compressor condensates in compliance with legal require-

ments. Your local “lower-level water authority” needs to 

be notified about the operation of the oil-water separator.

•  

KFC 25

:   Media / ambient temperature:   41...140 °F

 

KFC 50

:   Media temperature:  

41...140 °F

     

Ambient temperature:  

23...140 °F

  KFC only suitable for stationary application

•  KCF is not suitable for use in hazardous areas

Danger!

Compressed air!
Contact with quickly or suddenly escaping compressed air 

or with bursting plant components carries a risk of serious 

injury or death.

Caution!

Oil-contaminated condensate!
Oil-contaminated  condensate  contains  substances  that 

are hazardous both to health and the environment. These 

substances may cause irritation or damage to the skin, eyes 

and mucous linings. Oil-contaminated condensate must 

not be allowed to get into the sewer system, water bodies 

or the soil. Contaminated objects have to be cleaned or 

disposed of according to the legal regulations. 

 

Non-observance can result in injuries or damage to de-

vices! For the installation, the national regulations and 

safety instructions in force also need to be observed!

•  Only transport the KCF unit when it is empty!
•  Do not install the KCF outdoors!

Safety rules:

•  It is absolutely essential to observe the present Instructions 

for Installation and Operation.

Only use pressure-resistant installation material!

Ensure that condensate cannot squirt or splash onto 

persons or objects.

•  Protect the KCF against direct exposure to sunlight!
•  KCF 50: in the case of installation in a room where there 

is a danger of frost, a heating system has to be employed 

onl(optional)!

  Take measures to ensure that 

oil or untreated condensate 

cannot enter the sewer system in the event of damage!

  Do not fill any 

foreign liquid

 or substances into the prese-

paration tank / KCF since this may impair the filter function!

•  Only use original replacement filter sets!

  In  the  event  of  significant  differences  compared  with  the 

speci  fications of the general technical approval, e.g. the 

employment of non-original filters, the approval no longer cov

-

ers the usability of the KCF product. In such cases, individual 

approval of the responsible local authority will be required.

 

Moreover, there will be no entitlement to the remedy of 

defects within a 2-year period!

The operator’s duty of care includes the following:

Installation, siting, maintenance, repair or cleaning:
These tasks have to be carried out by a specialist firm, as 

required by law, unless the operator himself possesses the 

necessary qualifications and entitlements.

It should further be realised that the statutory limits for indirect 

clean-water discharge into the sewer system may   be subject 

to regional variations.

This work has to be documented in the operating manual. 

The operating manual and maintenance reports must be 

filed and presented to the responsible local authority if 

requested. 
Supervision:
The operator must ensure through constant monitoring 

that the KCF oil-water separator is in a leaktight condition 

and functioning correctly. 

•  Check the oil-water separator for leaks regularly!

  Check the outflowing clean water every week using the refer

-

ence test kit!

  Always keep a spare filter set!

Caution!
Oil-contaminated condensate!
Oil-contaminated  condensate  contains  substances  that 

are hazardous both to health and the environment. These 

substances may cause irritation or damage to the skin, eyes 

and mucous linings. Oil-contaminated condensate must 

not be allowed to get into the sewer system, water bodies 

or the soil. Contaminated objects have to be cleaned or 

disposed of according to the legal regulations. 

Содержание KCF 25

Страница 1: ...rfecto del KCF y de esta manera un tratamiento del con densado fiable Cher client Vous venez d acqu rir un s parateur huile eau KCF et nous vous en f licitons Nous vous recommandons de lire attentivem...

Страница 2: ...tion Putting into operation Operation Maintenance Waste water test KCF replacement filter sets Filter replacement General cleaning Components Indicaciones importantes Datos t cnicos Funcionamiento Ins...

Страница 3: ...le hebdomadaire de l eau Kit de filtres KCF Remplacement du filtre Nettoyage complet de l KCF Nomenclature des pi ces 4 8 10 12 14 16 16 18 18 18 20 22 Sommaire ndice Indica es importantes Dados t cni...

Страница 4: ...f installation in a room where there is a danger of frost a heating system has to be employed onl optional Take measures to ensure that oil or untreated condensate cannot enter the sewer system in the...

Страница 5: ...las normas de seguridad Transportar el KCF s lo en vac o No instalar el KCF en el exterior Proteger el KCF de la radiaci n solar directa KCF 50 Si se va a instalar el aparato en un recinto inte rior...

Страница 6: ...tall l ext rieur KCF doit tre prot g de toute exposition au soleil KCF 50 En cas d installation dans une pi ce qui ne serait pas l abri du gel il faut utiliser un syst me hors gel option En cas de dys...

Страница 7: ...te deve ser transportado quando vazio KCF n o deve ser disposto em reas externas KCF deve ser protegido contra incid ncia directa de raios solares Em caso de instala o em reas internas expostas a temp...

Страница 8: ...Poids vide Peso vazio 7 7 lb 12 7 lb Min max temperature Temperatura m n m x Temp rature min max Temperatura m n m x 41 140 F 41 140 F Max operating pressure at inlet Presi n de servicio m x entrada P...

Страница 9: ...rtie d eau sa da de gua P Sampling valve Grifo de toma de pruebas Prise d chantillon V lvula de tomada de amostra N Level indicator Indicador de nivel Indicateur de niveau Indicador de n vel inch KCF...

Страница 10: ...ssor Performance SCFM KCF Climate zone Piston Compressor Rotary Screw Compressor Mineral Oils Synthetic Oils Mineral Oils PAO Diester Oils Polyglycol Oils 25 1 COLD MILD 90 60 113 90 60 2 MEDIUM MODER...

Страница 11: ...de leo Atrav s da sa da de gua 6 a gua sai do KCF e pode ser conduzida de modo directo canaliza o A qualidade das guas servidas pode ser verificadaaqualquermomentojunto v lvula de retirada de amostra...

Страница 12: ...times have a downward slope of at least 1 Note Continuous slope Avoid water pocket of the feed hose to the pressure relief chamber Note Continuous slope Avoid sagging of the hose to the waste water ou...

Страница 13: ...a Sempre instalar o condutor principal de condensa o com inclina o cont nua no m nimo 1 Observe Inclina o cont nua Evitar bolsa de gua na mangueira de entrada da c mara de de descarga de press o Obser...

Страница 14: ...1 to ensure reliable functioning of the KFC 2 Installation See enclosed assembly drawing Floor mounting Use elongated holes of the 4 mounting 1 feet Screws and dowels supplied with unit Install the KF...

Страница 15: ...ensat au dessus du niveau sup rieur de le KCF Les flexibles doivent toujours tre fix s de fa on ce qu ils ne puissent pas se d placer sous l action d un coup de b lier et ne risquent pas de blesser qu...

Страница 16: ...ter through the inlet open ing container and filter chamber are filling up Shutoffthewaterwhenitstartstocome out at the water outlet The water level will sink due to the gradual water intake of the fi...

Страница 17: ...y pass Verificar as conex es quanto a estan queidade Paragarantirumfuncionamentoperfeito necess rio observar os pontos indica dos sob manuten o As subst ncias da condensa o do compressor dependem da r...

Страница 18: ...movel of material defects within the 2 years following the date of issue of the invoice will expire Remove the PE bag prior to inserting the filters and use it as a packaging for the used filter engli...

Страница 19: ...ra o filtro usado Avant chaque entretien Fermer l arriv e 1 si n cessaire arr ter le compresseur Maintanance V rifier r guli rement les flexibles et les raccords de flexibles 2 Remplacement du filtre...

Страница 20: ...id black cap Step 10 MUST BE COMPLETED before introducing compressed air condensate to unit Pour water into unit from the top through the pressure relief chamber area Step 11 Stop poring the water app...

Страница 21: ...tensio actifs tape7 Ins rerlanouvellecartouche dans le r servoir principal tape 8 Reposer le tuyau d amen e et aligner l encoche avec le couvercle une fois le tuyau d amen e mont ins rer un l ment fil...

Страница 22: ...R Y S u b j e c t t o R e v i s i o n KCF 25 50 22 Components Componentes Nomenclature des pi ces Componentes 1 2 3 4 5 6 11 9 10 12 8 13 5 7 15 16 17 16 1 2 3 4 5 6 11 9 10 12 8 13 5 7 13 13 14 15 16...

Страница 23: ...Angulo de montagem 14 Buj o 1 15 Empanque de cord o KCF 25 163 x 15 KCF 50 173 4x15 16 Empanque de cord o KCF 25 108 5 x 14 KCF 50 154 x 15 17 Anel em o 20 x 2 2 1 Tapa 2 Esterilla filtrante 3 Tubo d...

Страница 24: ...24_v01 Edition Estado Edition Data de refer ncia 2017 06 CANADA KAESER COMPRESSORS Inc 3760 La V rendrye Boisbriand QC J7H 1H5 Canada Phone 450 971 1414 Fax 450 971 1415 E mail info canada kaeser com...

Отзывы: