37
The ‘PRIMARY
STATUS L.E.D 1’ shows the first digit (tens) of the fault code and ‘
PRIMARY STATUS L.E.D 2’
shows the second digit (ones), e.g. fault code 35 would display as 3 flashes on ‘
PRIMARY STATUS L.E.D 1’ and
5 flashes on ‘
PRIMARY STATUS L.E.D 2’.
Both L.E.D’s will flash together for the first three flashes and then ‘PRIMARY STATUS L.E.D 1’ will stop while
‘PRIMARY STATUS L.E.D 2’ will flash two more times, example flash sequence below.
Primary Status L.E.D 1
Primary Status L.E.D 2
Some error codes that may be encountered during installation are detailed in Table 8 below.
9.4.2 Error codes associated with installation
Fault Code
Primary L.E.D 1
Flashes
Primary L.E.D 2
Flashes
Description
30
3
0
Fan Limp Mode
35
3
5
Supply Air Thermistor Fault
36
3
6
Bad Supply Air Thermistor Location
40
4
0
Return Air Overheat
41
4
1
Supply Air Overheat
48
4
8
Pressure Lost
60
6
0
Motor Open Circuit
69
6
9
Fuse Blown 24Vac 2A
50
5
0
Ignition Lockout
51
5
1
Rollout No Gas
54
5
4
Rollout Lockout
56
5
6
Pressure Switch Stuck Open
57
5
7
Pressure Switch Stuck Closed
58
5
8
Pressure Switch Fail
Table 8
To reset the appliance and clear a lockout fault press and hold the ‘CLEAR’ button for three seconds on the heater
control board or reset through a Networker controller if connected.
NOTE
The Kaden Networker controller is used as a Wired Wall Thermostat and is also the interface to
set Installer Parameters and obtain diagnostic information on the Kaden KUN4 and KUN5 Ducted
Gas Heaters. A spare Networker should be kept on hand for such purposes.
IMPORTANT
Ensure to advise the customer to visit
www.metaflex.com.au/kaden
and complete the online
warranty registration for their appliance.