9.2 INSTALLER PARAMETERS VIA NETWORKER
9.2.1 Networker Installer Parameter KUN4 & KUN5
No.
Display
Description
1
H01 ID01: 1350
HEATING: MAXIMUM FAN SPEED SETTING
The number displayed is the default fan speed setting. That is, the fan RPM setting for normal
heating operation. This setting can be adjusted from 500 to 1450 and should be set to meet
the installation airflow requirements. It is recommended that a fan speed of at least 1000 be
selected as lower speeds are more likely to result in overheating if the system has not been
balanced correctly.
2
H01 ID02: 1350
COOLING: MAXIMUM FAN SPEED SETTING
The fan RPM setting for normal cooling operation. This setting can be adjusted from 500 to
1350.
3
H01 ID03: 950
HEATING: ZONING MINIMUM FAN SPEED SETTING
The minimum RPM to which the fan will operate with the maximum number of outlets closed,
with the networker zoning in heating mode. This setting can be adjusted from 500 to 1350
(default is 950).
4
H01 ID04: 1
HEATER IDENTIFICATION NUMBER
(Do not alter unless multiple heaters are installed)
In systems with multiple heaters installed, identifies each heater unit in priority order, for
example ID04: 1, ID04: 2, ID04: 3.
5
H01 ID05: 500
CIRCULATION FAN OPERATION
The fan RPM setting in circulation mode. That is, fan operation between heating or cooling
cycles when the set room temperature has been achieved.
6
H01 ID06: 65
SUPPLY AIR THERMISTOR SET POINT TEMPERATURE
The temperature that the heater gas valve modulates to maintain. This setting can be
adjusted from 45°C to 70°C (default setting varies between different models) and should be
set to provide a comfortable outlet temperature.
7
H01 ID07: 0
ZONE/REFRIGERATION /HUMIDIFIER MODE
Value
System
Configuration
Zone
Connection
Add-On
Connection
Humidifier
Connection
0
Heating
N/A
N/A
N/A
1
Heating
Heater PCB – up to 4
N/A
N/A
2
H Add-On
Heater PCB – up to 4
Heater PCB
‘ADD-ON’ terminal
N/A
3
H
Humidification
Heater PCB – up to 4
N/A
Heater PCB ‘ADD-
ON’ terminal
4
H
Humidifi
Add-On
Heater PCB – up to 3
(A,B,C)
Zone Module – 1 only
(D)
Heater PCB
‘ADD-ON’ terminal
N/A
5
Heating
Zone Module – up to 4
N/A
N/A
6
H
Add-On
Zone Module – up to 4
Heater PCB
‘ADD-ON’ terminal
N/A
7
H
Add-On
Zone Module – up to 3
Zone Module
‘ADD-ON’ terminal
N/A
8
H01 ID08: 1000
COOLING: ZONING MINIMUM FAN SPEED SETTING
The minimum RPM to which the fan will operate with the maximum number of outlets closed,
with the networker zoning in heating mode.
DO NOT SET BELOW 1000
9
H01 ID09: 0
DO NOT ADJUST
10
H01 ID10: 30
Damper motor Open/Close time can be adjusted between 5 and 240 seconds - factory default
30 seconds