Maintenance/Troubleshooting
Page 47
Operating Instructions for Powador 7700-9600_EN
EN
Authorised electrician
Status
Display
!
Explanation
Action
By
FS
34
Communication
error
A communication error has occurred
in the internal data transmission.
"
Notify your author-
ised electrician.
E
FS
35
Protection
shutdown of the
software
Protective shutdown of the software
(AC overvoltage, AC overcurrent, DC
link overvoltage, DC overvoltage).
Not a fault
Grid-related
shutdown,
the grid connects
again automatically.
-
FS
36
Protective shut-
down of the hard-
ware
Protective shutdown of the
hardware (AC overvoltage, AC over-
current, DC link overvoltage).
Not a fault
Grid-related
shutdown,
the grid connects
again automatically.
-
FS
38
Error
PV overvoltage
The voltage of the DC generator is
too high. The PV generator is config-
ured incorrectly.
"
Notify your author-
ised electrician.
E
FS
41
Line failure:
undervoltage L1
The voltage of a grid phase is too
low; the grid cannot be fed into. The
phase experiencing failure is dis-
played.
"
Notify your author-
ised electrician.
E
FS
42
Line failure:
overvoltage L1
The voltage of a grid phase is too
high, the grid cannot be fed into.
The phase experiencing failure is
displayed.
"
Notify your author-
ised electrician.
E
FS
48
Line failure:
underfrequency
Grid frequency is too low.
This fault may be grid-related.
"
Notify your author-
ised electrician.
E
FS
49
Line failure:
overfrequency
Grid frequency is too high.
This fault may be grid-related.
"
Notify your author-
ised electrician.
E
FS
50
Line failure:
average voltage
The grid voltage measurement
according to EN 50160 has exceeded
the maximum permitted limit value.
This fault may be grid-related.
"
Notify your author-
ised electrician.
E
FS
51
Grid fault
(medium) over-
voltage L1
String voltage L1 is above the set
maximum permissible string voltage
"
Notify your author-
ised electrician.
E
FS
52
Grid fault
(medium) under-
voltage L1
String voltage L1 is below the set
minimum permissible string voltage
"
Notify your author-
ised electrician.
E
FS
53
Grid fault
(medium) over-
voltage L2
String voltage L2 is above the set
maximum permissible string voltage
"
Notify your author-
ised electrician.
E
FS
54
Grid fault
(medium) under-
voltage L2
String voltage L2 is below the set
minimum permissible string voltage
"
Notify your author-
ised electrician.
E
FS
55
Fault
DC link
Voltage at the DC link is too high, or
the DC link cannot be charged (IGBT
damage).
"
Notify your author-
ised electrician.
E
FS
56
SPI remote trip-
ping
Shutdown via digital input
Remote control for Italy CEI 0-21
Remote Trip-off
"
Notify your author-
ised electrician.
E
Table 8:
Operating status and fault messages on the display