Configuration and Operation
Page 37
Operating Instructions for Powador 7700-9600_EN
EN
Authorised electrician
Coun-
try-spec.
Settings
Menu
level
Display/
setting
Action in this menu/meaning
All countries
1
2
3
2
Quick start
Menu item is displayed only when waiting for grid feed
and during ramp-up limiting.
Offers the option of ramping up the inverter faster for
inspection or testing.
If there is insufficient PV array power, the inverter stops
feeding into the grid after a short period of time.
All countries
1
2
3
3
"Parameters" menu
Only service technicians are permitted to make changes
in the parameter menu.
↻
You are in menu level "1".
"
Press "2" for at least 15 seconds to open menu level 3.
1
2
3
3
Select country
The default setting is used if "no" is selected
.
"
Set the desired country setting.
NOTE:
This option influences the country-specific operat-
ing settings of the inverter. Please consult KACO service
for further information.
All countries
1
2
3
3
Set grid
parameters
"
Provides the option to set the grid parameters.
1. Confirm "Yes" input using "1" key.
2. Set the required grid parameters in the next menu.
"
If "No" is selected, the defined country-specific
parameters will be used.
DE-MSP, ES,
GB, FR-HTA,
IT-CEI021,
UD, IL
Undervoltage
shutdown
"
Specify the shutdown threshold
for fast and slow undervoltage shutdown.
"
Set period from occurrence of the fault to shutdown
of the inverter.
DE-MSP, ES,
GB, FR-HTA,
IT-CEI021,
UD, IL
Overvoltage
shutdown
"
Specify the shutdown threshold
for fast and slow overvoltage shutdown.
"
Set period from occurrence of the fault to shutdown
of the inverter.
DE-NSP, BE
"
Activate or deactivate password protection.
"
Specify the shutdown threshold
for overvoltage shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.
"
Set period from occurrence of the fault to shutdown
of the inverter.
AT, BG, CZ,
FR (not HTA),
PF, DE-VDN
Max. line voltage
EN 50160
The grid voltage is averaged over ten minutes. If the
defined value is exceeded, the inverter is disconnected
from the grid.
"
Set voltage threshold.
Voltage drop
between meter and
inverter
The voltage drop between the inverter and the grid-feed
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.
"
Specify the switch-off value for the voltage drop (0 to
11 V).