Installing the inverter
Page 24
Operating Instructions for Powador 7700-9600_EN
EN
EN
Authorised electrician
7.3.3 Connecting the RS485 bus
NOTE
Ensure that the A and B wires are properly connected. Communication is not possible if the wires are
reversed.
7.3.3.1 Wiring diagram
KACO
Inverter
KACO
Inverter
KACO
Inverter
KACO
Monitor-
ing
system
Figure 18: RS485 interface wiring diagram
KACO
Inverter
KACO
Inverter
KACO
Inverter
KACO
monitor-
ing system
Figure 19: RS485 interface wiring diagram with CAN (RJ45) connection
Properties of the RS485 data line
Maximum length of the RS485
bus line
The maximum allowed length of the RS485 bus is 1200 m.
This length can be reached only under optimum conditions.
Cable lengths exceeding 500 m generally require a repeater or a hub.
Maximum number of
connected bus devices
31 inv 1 data monitoring unit
Data line
Twisted, shielded. Recommendations:
LI2YCYv (twisted pair) black for laying cable outside and in the ground, 2 x 2 x 0.5
LI2YCY (twisted pair) grey for dry and moist indoor spaces, 2 x 2 x 0.5
NOTE
Different manufacturers do not always interpret the standard on which the RS485 protocol is based
in the same way. Note that the wire designations (- and +) for wires A and B can vary between manu-
facturers.
NOTE
Calculating efficiency by measuring the current and voltage values can lead to misleading results
due to the tolerances of the measurement devices. The sole purpose of these measured values is to
monitor the basic operation of the system.
Term
RS485
RS485
ON
A B
Term
RS485
RS485
OFF
Term
RS485
RS485
OFF
A B
A B
Term
ON
ON
A
B
SYM-Bus
CAN
CAN
A
B
RS485
RS485
CAN
RJ45
RS485
CAN
CAN
Term
A
OFF
RS485
SYM-Bus
RJ45
CAN
OFF
B
RS485
ON
SYM-Bus
RS485
Term
CAN
B
OFF
CAN
RJ45
CAN
A
Patch-Cable