Configuration and Operation
Page 36
Operating Instructions for Powador 7700-9600_EN
EN
EN
Coun-
try-spec.
Settings
Menu
level
Display/
setting
Action in this menu/meaning
All countries
1
2
3
2
Language
"
Select the desired menu language.
1
2
3
2
Date/Time
Set date and time with an additional PCB installed. (real-
time module RTC)
1
2
3
2
Clear grid-feed
meter
Allows the grid-feed meter to be cleared.
("Yield" meter and "Operating hours" meter)
"
If "yes" is selected the password is requested.
"
Setting required password number "2"
If the code number is valid, the grid-feed meter is
cleared and a confirmation is displayed with "Grid meter
cleared!".
1
2
3
2
Defining total
yield
You can set the total yield to any value, for example,
when you have received a replacement unit and want to
continue the recording from the present value.
"
Select "yes" to set the total yield.
1
2
3
2
Interface
Select the RS232 or RS485 interface for data transmission
(For unit series 7700-8600 only)
"
The interface is changed by pressing "2".
1
2
3
2
Inverter address
A unique address must be defined for every inverter with
an active RS485 interface. The interface is used to com-
municate with the Powador-proLog.
"
By pressing key “2”, the RS485 address can be set con-
secutively from 1 to 32.
1
2
3
2
S0 interface
Selection of pulse rate for the S0 interface
500, 1000 and 2000 pulses/kWh
"
Set pulse rate.
1
2
3
2
Activate priwatt
Enables the use of the fault signal relay for the
Powador-priwatt internal consumption control relay.
"
Activate or deactivate the home feed-in function.
NOTE:
Activating this option enables the
Set priwatt
menu option.
1
2
3
2
Set priwatt
"
Define the switch-on power in kW that needs to be
available on an uninterrupted basis for 30 minutes
before the home feed-in is activated.
"
Define the switch-on time (operating time of Pow-
ador-priwatt after activation).
NOTE:
This menu item is only available if you have
selected the “On” option for the “Activate priwatt” menu
item in the “Settings” menu.
All countries
(except DE-
MSP)
1
2
3
2
Power Boost
Offers the option of reducing the frequency of the IGBT
bridge from 17 kHz to 9 kHz to improve efficiency.
"
Power Boost mode is activated by pressing "2". NOTE:
The change may cause operating noise.