Configuration and Operation
Page 42
Operating instructions KACO blueplanet 50.0 TL3 S/Basic/M/XL
EN
EN
Country-spec.
Setting
Menu
level
Display/setting
Action in this menu/meaning
BE, CH-NS, CY,
DE-NS, DK,
LU-NS
4
1
2
3
1
Frequency shut-
down
The inverter continuously monitors the grid frequency.
If the grid frequency exceeds or drops below the con-
figured values, the inverter switches off.
"
Set limit values for underfrequency and overfre-
quency in 0.1 Hz increments.
"
Set period from occurrence of the fault to shut-
down of the inverter.
All countries
4
1
2
3
1
Activation
condition
NOTE:
The inverter checks mains voltage and fre-
quency. The grid feed operation begins if the measured
values are within the set ranges.
"
Set minimum and maximum values for connection.
4
1
2
3
1
Connection time
"
Set period for grid observation (in seconds) when
switching on and reconnection after a fault.
4
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this DC voltage
is present.
"
Set the starting voltage.
4
1
2
3
1
SPD monitoring
NOTE:
Please refer to the application note on our
home page if you install the overvoltage protection by
yourself.
Allows monitoring of the overvoltage protection.
"
Activate overvoltage protection.
NOTE:
By activating, an overvoltage protection test is
carried out with an appropriate status message.
4
1
2
3
1
Constant volt. con-
trol
NOTE:
Possibility to deactivate the MPP seek mode in
order to operate the device with a constant DC voltage.
"
Activate or deactivate the constant voltage con-
troller.
"
Set value for constant voltage control.
4
1
2
3
1
Power limitation
NOTE:
The output power of the inverter can be set per-
manently to a lower value than the maximum output
power by the internal power limitation.
This may be necessary in order to limit the maximum
power rating of the system at the grid connection
point, upon the grid operator's request.
The value can be protected from the very first power
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specific pass-
word.
1. Activate or deactivate password protection
2. Specify activation status (on/off )
3. Specify limit value for maximum feed-in
power
4. Confirm the entry with the Enter button.