
Configuration and Operation
Page 40
Operating instructions KACO blueplanet 50.0 TL3 S/Basic/M/XL
EN
EN
Country-spec.
Setting
Menu
level
Display/setting
Action in this menu/meaning
All countries
4
1
2
3
3
“Parameters” menu
"
Press the right arrow button or the Enter button.
NOTE:
The inverter does not display the “Parameters”
menu in the standard configuration. To display the
Parameters menu:
1.
Open the menu.
2. Simultaneously hold down the up and down but-
tons for several seconds.
4
1
2
3
1
Country
NOTE:
This option influences the country-specific
operating settings of the inverter. Please consult KACO
service for further information.
1.
Enter the four-digit password using the 4-way
button. The password is unit-specific.
2. Confirm the entry with the Enter button.
3. Set the desired country setting.
CH, DE, ES, FR,
GB, GR, IT, JO,
JP, LU, TH, ZA
4
1
2
3
1
Grid type/guideline
"
Select the grid type for the inverter’s installation
location.
UD
4
1
2
3
1
Mains rated voltage
"
Set the specified grid voltage for the site where the
unit is used (please contact KACO Service)
All countries
4
1
2
3
1
Grid parameters
"
Open the menu: Press the right arrow button or
the Enter button.
AT, BG, CZ,
FR-OLD,
FR-VFR13,
FR-VFR14, IE,
JP, NL, PL, PT,
TR, TW, UD
4
1
2
3
1
Overvoltage shut-
down, 10 min. aver-
age
"
Activate or deactivate password protection (coun-
try-specific password protection!).
"
Specify the shutdown threshold
for overvoltage shutdown. The 10-minute average
for the measured voltage as per EN50160 is used.
"
Set period from occurrence of the fault to shut-
down of the inverter.
BE
, CH-NS
, CY
,
DE-NS
, DK
, LU-NS
FR-OLD,
FR-VFR13,
FR-VFR14, JP,
UD
4
1
2
3
1
Voltage drop
NOTE:
The voltage drop between the inverter and the
feed-in meter is added to the limit value that was set
for grid shutdown according to EN 50160. The limit
value can be set from 0-11 V in 1 V increments.
"
Specify the shutdown value for the voltage drop
(0-11 V).
AT, AU, BG,
CH-MS, CZ,
DE-MS, ES, FR,
GB, GR,HR,
HU, IE, IL, IN,
IT, JO, JP, KR,
NL, PL, PT, RO,
TH, TR, TW,
UD, ZA
4
1
2
3
1
Overvoltage shutd.
"
Specify the shutdown threshold for fast and slow
overvoltage shutdown.
"
Set period from occurrence of the fault to shut-
down of the inverter.
4
1
2
3
1
Undervoltage shutd.
"
Specify the shutdown threshold
for fast and slow overvoltage shutdown.
"
Set period from occurrence of the fault to shut-
down of the inverter.
Содержание blueplanet 50.0 TL3 S
Страница 2: ...The copyright for these operating instructions is held solely by KACO new energy GmbH...
Страница 66: ......
Страница 67: ......