Reference power

 Actual power |

Nominal power

F

Select the power-dependent control method.

4

1

2

3

4

Evaluated voltage

Maximum phase

voltage | Positive
phase sequence
voltage

F

Select the voltage to be rated.

Specifies which voltage is evaluated in a three-phase system.

4

1

2

3

4

Hysteresis mode

Off | On

NOTE: Hysteresis mode affects the shutdown response of
P(U).

F

Activate the mode.

4

1

2

3

4

Deactivation gradient

 1 - 65534 [% / min]

F

Set gradients for the voltage limitation.

4

1

2

3

4

Deactivation time

 0 – 60000000 [ms]

F

Specify the time for voltage reduction.

4

1

2

3

4

Active curve

 1 - 5

F

Select active curve.

NOTE: Up to 5 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.

4

1

2

3

4

Number of nodes

 2 – 5

F

Specify the number of nodes.

Power

 0.0 -100.0 [%]

F

Specify power for 1st, 5th ... node as a percentage of the maximum
power.

Voltage

 0.0 -126.0 [%]

Password protection

 Status

1. Specify voltage for 1st, 5th ... node as a percentage of the maximum

voltage.

2. Activate optional password protection.

3. Confirm the action field.

4

1

2

3

4

Activation threshold

 230V – 276V

F

Specify the activation threshold.

NOTE: If the 10 min mean value of the voltage exceeds the ac-
tivation threshold, then the function is enabled. The power
level is adjusted in such a way that the instantaneous effective
voltage value does not exceed the activation threshold value.

4

1

2

3

4

Deactivation threshold

 230V – 276V

.

NOTE: If the 10 min mean value of the voltage falls below
the deactivation threshold, then the function is disabled.

1. Specify the deactivation threshold.

4

1

2

3

4

Upload/download

NOTE: Opportunity to save log files and save and import para-
meter data

Download service log
data

F

Save service log data to external storage media.

Download service log
data without yields

F

Save log data without yields to external storage media.

Download a set of
parameters

F

Save a set of parameters to external storage media.

Document a set of
parameters

F

Issue or print documentation of a set of parameters as a PDF.

Transfer a set of para-
meters

F

Load a set of parameters from external storage media.

9 | Configuration and operation

Manual

KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO

blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3

Page 50

EN

Содержание blueplanet 3.0 TL3 M2 WM OD IIG0

Страница 1: ...3 KACO blueplanet 6 5 TL3 KACO blueplanet 7 5 TL3 KACO blueplanet 8 6 TL3 KACO blueplanet 9 0 TL3 KACO blueplanet 10 0 TL3 These instructions form part of the product and must be carefully read observ...

Страница 2: ...me In this the product Photovoltaik Netzeinspeise Wechselrichter Designated as a unit for reading reasons Trademarks All brand and product names used in this document are trademarks or registered trad...

Страница 3: ...ing the connection area 30 8 Commissioning 31 8 1 Requirements 31 8 2 Preconditions relating to standards 31 9 Configuration and operation 32 9 1 Initial start up 32 9 2 Signal elements 32 9 3 User in...

Страница 4: ...m firmware version onwards Type designation KACO article No KACO blueplanet 3 0 TL3 M2 WM OD IIG0 1001670 KACO blueplanet 4 0 TL3 M2 WM OD IIG0 1001671 KACO blueplanet 5 0 TL3 M2 WM OD IIG0 1001205 KA...

Страница 5: ...w risk hazard Failure to observe this warning will lead to minor or moderate bodily injury CAUTION Risk of damage to property Failure to observe this warning will lead to property damage 1 3 3 Additio...

Страница 6: ...ng to country speci c requirements details see manual No galvanic separation UTILITY INTERCONNECTED Fig 1 Name plate 1 5 Warnings on the device A warning sticker is affixed to the device Read the warn...

Страница 7: ...surroundings of the device must comply with the applicable national and local standards When working on the PV generator in addition to disconnecting this from the grid it is also necessary to switch...

Страница 8: ...otect the power semiconductors from high energy transients on the grid and generator sides Device temperature monitoring system EMC filter to protect the inverter from high frequency grid interference...

Страница 9: ...tion area 9 DC isolator switch 5 AC connection 5 pole connector 3 2 1 Mechancial Components The DC isolator switch is located on the underside of the device The DC isolator switch is used to disconnec...

Страница 10: ...USB connection of the device is a type A socket It is located on the underside of the housing and is protec ted by a safety cover The USB connection is specified to draw 500 mA of current Use the USB...

Страница 11: ...panies also allow the installation of your own calibrated meters Selective main switch The selective main switch is to be specified by the power supply company Reference counter The reference counter...

Страница 12: ...3x 12 00 A 415V 3x 12 50 A 400V 3x 13 10 A 380V 3 x 12 60 A 415V 3 x 13 00 A 400V 3 x 13 70 A 380V 3x 14 95 A 415V 3x 14 50 A 400V 3x 15 20 A 380V Max continuous current 3 x 4 8 A 3 x 6 4 A 3 x 8 0 A...

Страница 13: ...unit no Protection class over voltage category I III AC II DC Grid monitoring Country specific Distribution system TN C System TN C S System TN S System TT System 3 0 TL3 4 0 TL3 5 0 TL3 6 5 TL3 7 5...

Страница 14: ...n level outside the en closure 3 Item number 1001670 1001671 1001205 1001204 1001203 1001461 1001202 1001460 Name on nameplate KACO blue planet 3 0 TL3 M2 WM OD IIG0 KACO blue planet 4 0 TL3 M2 WM OD...

Страница 15: ...due to impact risk of breakage to the device 1 Pack the device securely for transport 2 Transport the device using the intended carrying handles of the packaging box 3 Do not expose the device to any...

Страница 16: ...the manufacturer warranty NOTE Access by maintenance personnel for service Any additional costs arising from unfavourable structural or installation conditions will be billed to the cus tomer Install...

Страница 17: ...Lift the unit Key 1 Packaging 3 Device 2 Protective packaging 4 Grip recesses The device is transported to the installation location 1 Loosen packaging tape from cardboard box 2 Open carton at the fro...

Страница 18: ...18 A Minimum clearance 150 mm without device304 5 mm recommended distance475 mm without device 510 mm C Minimum clearance 700 mm B Minimum clearance 500 mm D Recommended clearance 250 mm Cardboard pac...

Страница 19: ...N O 4 3 Fig 15 Mounting the device Key 1 Opening 3 Insertion lugs 2 Centre of gravity 4 Mounting bracket Lifting and installing the device The mount has been installed 1 Lift the device using the lat...

Страница 20: ...n the connection area until you perform installation 1 Seal off any plug in connections and screw fittings using sealing covers 2 Prior to installation check the inner area for condensation and if nec...

Страница 21: ...ty value in accordance with the following basic conditions Country specific installation standards power rating of the device cable length type of cable installation local temperature 7 2 1 Requiremen...

Страница 22: ...eter used 3 Slide the housing and seal over the cable 4 Remove the insulation from the cable sl 50 mm 5 Shorten the wires N L1 by 8 mm if a single phase connection is present or shorten the wires N L1...

Страница 23: ...see See section 9 4 1 Page 35 For questions regarding the appropriate type please contact the installer or our KACO new energy customer service NOTE When the line resistance is high i e long cables on...

Страница 24: ...ve recommended standard connection 1 A B 2 UMPP n1 n2 Fig 25 Recommended standard connection 1 A B 2 UMPP n1 Fig 26 Parallel input with Y adapter short circuits the unused MPP Tracker B 1 A B 2 UMPP n...

Страница 25: ...ea opened NOTE Before proceeding with the isolation ensure that you do not cut any individual wires 1 Strip the wires for DC connection sl 2 Insert isolated wires with twisted ends carefully up to the...

Страница 26: ...ltage on the open ends of the DC cables 1 Only touch the PV generator cables on the insulation Do not touch the exposed ends of the cables 2 Avoid short circuits 3 Do not connect any strings with a gr...

Страница 27: ...d lock washer provided W_T30 2 2 Nm 4 Check that the connected cable is fitted securely The housing is included in the equipotential bonding 1 Fig 32 Additional grounding point 1 Earthing bolt 7 6 Con...

Страница 28: ...t into the cable fitting 5 Feed the connection cables into the connection area Ethernet cable inserted 2 1 Fig 34 Inserting the interface cable 1 Cable fitting for pass the Eth ernet cable 2 Cable fit...

Страница 29: ...eeding 500 m generally require a repeater or a hub Maximum number of connected bus devices 99 devices 1 data monitoring unit Data line Twisted shielded Recommendation Li2YCYv twisted pair black for la...

Страница 30: ...over of the device has been opened 1 Undo the cable fittings W_20 2 Pass the connection cable through the cable fittings 3 Connect wire A to the terminal marked INV OFF on the first device via the DO1...

Страница 31: ...feed in mode Accordingly the self test menu dialogue is not visible if the inverter is disconnection from the grid A corresponding remote control com mand for starting the self test function via the R...

Страница 32: ...EDs on the device control panel show the different operating states The LEDs can display the following states LED illuminated LED flashing LED not illuminated Operating status LED Icon Display Descrip...

Страница 33: ...Status bar 6 Daily yield 3 Current time 7 Menu indicator 4 Feed in indicator 8 Current power Graphical display The graphical display shows measured values and data and allows the configuration of the...

Страница 34: ...F Use the up button or down button to navigate Opening a menu item or a setting F Use the right arrow button and the Enter button Navigate to the next higher menu level discard change F Use the left...

Страница 35: ...ons displayed on screen are dependent on the country and network settings and may vary ac cording to the type of device Functions restricted to one or more countries are labelled with country codes in...

Страница 36: ...Press the Right arrow button or Enter button 4 1 2 3 4 Daily view NOTE Displays the recorded operating data graphically F Select the measured value to be displayed Supported measured values 1 Grid po...

Страница 37: ...ime span during which the power threshold must be exceeded without interruption 4 1 2 3 4 Power threshold F Set power threshold from which the monitoring time up to activation begins 4 1 2 3 4 Operati...

Страница 38: ...server F Open the menu Press the Right arrow button or Enter button 4 1 2 3 4 Operation mode F Activate or disable the integrated web server 4 1 2 3 4 Port F Set the port at which the web server can b...

Страница 39: ...rvice 4 1 2 3 4 Grid parameter F Open the menu Press the Right arrow button or Enter button AT BG CZ FR OLD FR VFR13 FR VFR14 IE JP NL PL PT TR TW UD 4 1 2 3 4 Overvoltage shutd 10 min average 1 Speci...

Страница 40: ...hutdown threshold for fast and slow overvoltage shut down 2 Set period from occurrence of the fault to shutdown of the device See Over voltage shutd 4 1 2 3 4 Undervoltage shutd 1 Specify the shutdown...

Страница 41: ...cy shutd NOTE The device continuously monitors the grid frequency If the grid voltage exceeds or drops below the configured val ues the device switches off 1 Set limit values for underfrequency and ov...

Страница 42: ...rametrization possible via WEBGUI 4 1 2 3 4 Powador protect Auto On Off NOTE Configures the support for grid shutdown via a Powador protect connected to the INV OFF input of the device Auto On A Powad...

Страница 43: ...in 0 00 per thousand 4 1 2 3 4 Deact grad F Specify deactivation gradient in 0 00 per thousand minute if mode 1 or mode 2 is active This menu option is displayed permanently for IT and IL 4 1 2 3 4 Fa...

Страница 44: ...power as of rated power above which control is ac tivated 4 1 2 3 4 Lock Out power 0 100 Smax F Set the active power as of rated power below which control is de activated 4 1 2 3 4 Lock in time 0 s 6...

Страница 45: ...s possible via the web interface BE CH NS CY DE NS DK JP 50HZ JP 60HZ LU NS TW UD 4 1 2 3 4 Grid errors NOTE Display of grid faults F To show the last 5 grid fault messages press the Show button 4 1 2...

Страница 46: ...Off Deactivates dynamic grid support using dynamic reactive current Dynamic grid support remains active on account of immunity to inter ference Setting Manual Pre defined zero current F Select a contr...

Страница 47: ...ure Max conn voltage after grid failure F Set min and max switch on voltage after grid monitoring 4 1 2 3 4 Min conn frequency after grid failure Max conn frequency after grid failure F Set min and ma...

Страница 48: ...NOTE The output power of the device can be set permanently to a lower value than the maximum output power by the in ternal power limitation This may be necessary in order to limit the maximum power r...

Страница 49: ...l password protection 3 Confirm action field 4 1 2 3 4 Priority mode Q Priority P Prior ity F Set priority for reactive power Q or active power P NOTE When it comes to P priority the reactive power ad...

Страница 50: ...tivation threshold 230V 276V F Specify the activation threshold NOTE If the 10 min mean value of the voltage exceeds the ac tivation threshold then the function is enabled The power level is adjusted...

Страница 51: ...A If a device with a higher power requirement is used the power supply for the USB in terface automatically shuts down to protect the device from damage Web server This device has an integrated web se...

Страница 52: ...the buttons daily view monthly view yearly view or overview Filtering the display period only possible with daily view 1 Open the web server 2 Select the daily view 3 To show or hide measurements sele...

Страница 53: ...quired The following message appears if the DC power supply is too low DC power supply too low Perform update anyway In this case select No and perform the update with a stable power supply f the unit...

Страница 54: ...high level of process reliability Firmware version of device is identical to the specifications of the Sunspec Modbus 1 Enable the entry Network Modbus TCP Operation mode Network services Modbus TCP...

Страница 55: ...with a nominal voltage of 277 480 correspond to the first figure tak ing into consideration the voltage values in this table 1 P p u Q P u 0 6 0 4 0 2 0 1 0 8 1 2 0 6 0 6 1 0 0 above 390V at 380V at...

Страница 56: ...t receive a new power factor spe cification falls back to the previously valid reactive power procedure If the timeout is set to 0 seconds the transmitted power factor specification is permanently ret...

Страница 57: ...this case a characteristic curve is specified which can be used to configure up to 10 nodes value pairs for active power and cos The active power is entered as a in relation to the nominal power Othe...

Страница 58: ...be 0 for the last node the power must be 100 The power values of the nodes must increase continu ously Note Storage inverters only for feed in operation 0 100 cos of the node Over excited un der exci...

Страница 59: ...mber of nodes 2 10 Specify the number of nodes for the Q U characteristic curve 1st node 10th node 0V Max voltage in continuous operation Voltage of the node in volts The voltage values of the nodes m...

Страница 60: ...is the function is activated as soon as the voltage exceeds the configured voltage of data point 1 dp1 The power limit follows the characteristic curve a straight line between dp1 and dp2 The function...

Страница 61: ...of a change in the act ive power set value With a voltage change the active power is changed according to a PT 1 characteristic curve with a settling time of 5 Tau Note The settling time is overlaid...

Страница 62: ...connection guidelines prohibit adjustments Adjusting the active power P f in the event of underfrequency Some grid connection guidelines also require adjustment of the active power P f in the event o...

Страница 63: ...n order to prevent any negative impact on is land detection However P f has no negative impact on KACO s en hanced island detection Frequency of the max imum deactivation threshold 45 50 2 Hz Frequenc...

Страница 64: ...is overlaid with the settling time 10 3 FRT Dynamic grid support Fault Ride Through A generation plant s ability to remain immune to voltage drops and voltage spikes in the supply system is a key ele...

Страница 65: ...reactive current corres ponds to an inductive load In the reactive current priority mode the effective current is reduced to the extent necessary to comply with the limits of the maximum continuous c...

Страница 66: ...e configured only the activation threshold for zero current has to be configured Priority Reactive cur rent limitation Active current priority Priority Reactive current priority Dynamic grid support a...

Страница 67: ...ode 1 Mode 2 Mode 1 When calculating the reactive current the value of the dead band is not subtracted from the amount of voltage change As such formula 2 applies to overvoltage and undervoltage incid...

Страница 68: ...ximum active power of the plant Fig 58 P Q operating range with limited active power Qmax Smax Pmax for PV inverters The power reduction parameters can be adjusted in SunSpec model DID123 During this...

Страница 69: ...of the grid will remain live in an unintended island due to the balance of load and generation in this part of the grid The detection of uninten ded island formation is an important function of decen...

Страница 70: ...thin some 100 ms well below 1000 ms The number of parallel inverters does not affect the reliability of this function This method also guarantees the minimisation of effects on the distribution grid I...

Страница 71: ...fore opening the device Disconnect the AC and DC sides and wait at least 5 minutes NOTE There are components in the housing of the device which may only be repaired by the customer service team 1 Do n...

Страница 72: ...basis 3 Remove dust from the ventilation inlets if necessary 11 2 2 Cleaning the heat sink NOTE Refer to our service and guarantee conditions on our homepage The cleaning intervals must be adapted to...

Страница 73: ...er 2 Latch fan into latch bracket 3 Plug in the fan plug 4 Place fan cover onto fan cavity and fix in place with the fastening screws The replacement fan is ready for operation Switch unit on 4 3 1 2...

Страница 74: ...Grid feed is interrupted due to a grid fault Due to a grid fault over undervoltage over underfrequency the device stopped the feed in process and disconnected from the grid for safety reasons Change...

Страница 75: ...are able to hear the high fre quency hum caused by the device s operating frequency of ap proximately 17 kHz No action In spite of high radiation levels the inverter does not feed the maximum power in...

Страница 76: ...or voltage fails under load in sufficient DC power a Compare the voltage measured with the no load voltage expected b Check if the DC isol ator switch is switched off c Check whether a D B 3 Constant...

Страница 77: ...discon nection or External grid protection shutdown The activated grid and system protection has been tripped If the Powador pro tect is not required please check in the menu to see if Ac tivate Powa...

Страница 78: ...resolve the is sue notify your au thorized electrician B E 32 Self test error The internal grid separation relay test has failed Notify your author ized electrician if the fault occurs re peatedly E...

Страница 79: ...undervoltage L3 See description in the event of a fault 41 See action in the event of a fault 41 E 46 Grid failure overvoltage L3 See description in the event of a fault 41 See action in the event of...

Страница 80: ...en cer tain country settings are activated the fre quency dependent power change is activated Normative require ment 64 Output current limitation Output current limiting The AC current is lim ited onc...

Страница 81: ...ec ted the device to protect it against damage In case of repeated occurrence Contact a qualified electri cian E 87 Protection shutdown over current L1 A current that has been found on a conductor is...

Страница 82: ...has shut down because of implaus ible internal measured values Notify KACO Ser vice K 105 Plausibility fault relay The device has shut down because of implaus ible internal measured values Switch off...

Страница 83: ...voltage measurement technology error AC voltage measurement technology error Shutdown because the voltage meas urements upstream of and between the relays do not match F127 exited after 3 s E 128 Inte...

Страница 84: ...r message merely a protective func tion of the inverter to prevent the capacity of the input from being exceeded Input power limitation DC1 The DC input power is limited once the specified maximum val...

Страница 85: ...e falls below the set value Insulation error close to the centre of the PV string area covering 15 of the half of the string Insulation errors must be rectified in order to operate the system safely a...

Страница 86: ...ing or missing AC voltage can in dicate this connec tion problem B 204 Protection shutdown grid volt L2 See description in the event of an error 203 See action in the event of an error 203 B 205 Prote...

Страница 87: ...quence be carried out in the correct order 1 Check that there is no current in any of the DC cables using a clip on ammeter WARNING Risk of burns caused by hot housing components Housing components ca...

Страница 88: ...pen and maintain the device 2 Before opening the device Disconnect the AC and DC sides and wait at least 5 minutes Device disconnected and secured against restart 1 Undo the 2 screws and carefully rem...

Страница 89: ...nt conditions or temporary relocation from a cold to a hot environment 1 Prior to installation check the inner area for condensation and if necessary allow it to dry sufficiently be fore installation...

Страница 90: ...faulty devices or accessories together with household waste Ensure that the old devices and any accessories are disposed of in a proper manner Packaging Ensure that the transport packaging is disposed...

Страница 91: ...ith telephone number Information about the accessibility of the installation site You can find the following items and other information at our web site Kaco newenergy our current warranty conditions...

Страница 92: ...irective relating to electrical equipment designed for use within certain voltage lim its EN 62109 1 2010 EN 62109 2 2011 2014 30 EU Interference immunity Directive relating to electromagnetic com pat...

Страница 93: ...nt technical state at the time of printing Subject to technical changes No liability for printing errors Werner von Siemens Allee 1 74172 Neckarsulm Germany Tel 49 7132 3818 0 info kaco newenergy de w...

Отзывы: