4
1
2
3
4
Reference power
Actual power |
Nominal power
F
Select the power-dependent control method.
4
1
2
3
4
Evaluated voltage
Maximum phase
voltage | Positive
phase sequence
voltage
F
Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
4
1
2
3
4
Hysteresis mode
Off | On
NOTE: Hysteresis mode affects the shutdown response of
P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
1 - 65534 [% / min]
F
Set gradients for the voltage limitation.
4
1
2
3
4
Deactivation time
0 – 60000000 [ms]
F
Specify the time for voltage reduction.
4
1
2
3
4
Active curve
1 - 5
F
Select active curve.
NOTE: Up to 5 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
4
1
2
3
4
Number of nodes
2 – 5
F
Specify the number of nodes.
Power
0.0 -100.0 [%]
F
Specify power for 1st, 5th ... node as a percentage of the maximum
power.
Voltage
0.0 -126.0 [%]
Password protection
Status
1. Specify voltage for 1st, 5th ... node as a percentage of the maximum
voltage.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Activation threshold
230V – 276V
F
Specify the activation threshold.
NOTE: If the 10 min mean value of the voltage exceeds the ac-
tivation threshold, then the function is enabled. The power
level is adjusted in such a way that the instantaneous effective
voltage value does not exceed the activation threshold value.
4
1
2
3
4
Deactivation threshold
230V – 276V
.
NOTE: If the 10 min mean value of the voltage falls below
the deactivation threshold, then the function is disabled.
1. Specify the deactivation threshold.
4
1
2
3
4
Upload/download
NOTE: Opportunity to save log files and save and import para-
meter data
Download service log
data
F
Save service log data to external storage media.
Download service log
data without yields
F
Save log data without yields to external storage media.
Download a set of
parameters
F
Save a set of parameters to external storage media.
Document a set of
parameters
F
Issue or print documentation of a set of parameters as a PDF.
Transfer a set of para-
meters
F
Load a set of parameters from external storage media.
9 | Configuration and operation
Manual
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Page 50