ROCOF threshold stage
1 value 0.1 – 6.0
[Hz / s]
ROCOF threshold stage
2 value 0.1 – 6.0
[Hz / s]
F
Define threshold for ROCOF.
ROCOF threshold stage
1 time 0.10 – 5.00
[ s]
ROCOF threshold stage
2 time 0.10 – 5.00
[ s]
F
Define time value for ROCOF.
4
1
2
3
4
Change password for
“installer”
Password of the
logged-on user | New
password for the “in-
staller” access | Con-
firm new password
1. Enter old password.
2. Enter a new, secure password.
3. Confirm and apply new password.
4
1
2
3
4
Change password for
"user"
Password of the
logged-on user | New
password for the
"user" access | Confirm
new password
1. Enter old password.
2. Enter a new, secure password.
3. Confirm and apply new password.
4
1
2
3
4
10 min. average
Overvoltage aver-
aging
F
Set the voltage via averaging.
Counter / inverter
voltage drop
F
Set the voltage.
4
1
2
3
4
Power Limitation
NOTE: The output power of the device can be set permanently
to a lower value than the maximum output power by the in-
ternal power limitation. This may be necessary in order to
limit the maximum power rating of the system at the grid
connection point, upon the grid operator's request.
4
1
2
3
4
Internal
NOTE: Opportunity to limit the power internally More detailed
information at:
4
1
2
3
4
Power Limitation
Status
F
Specify the activation status.
4
1
2
3
4
Maximum apparent
power Slim
1000 – S
max
[VA]
NOTE: The max. apparent power limits the internal power of
the device.
F
Enter the value or set the value using the slider.
4
1
2
3
4
Maximum active power
Plim
1.0 - 100.0 [% Slim]
Password protection
Status
F
Enter the value or set the value using the slider.