Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Grid parameter (fur-
ther information)
U<<
U<
U
con,min
U>
U>>
U
con,max
f<<
f<
U
con,min
f>
f>>
U
con,max
I
f the value U< (slow undervoltage shutdown) is set to a value which is
greater than the value of U
con
,
min
(minimum restart voltage) using the LC
display, then the value of U
con
,
min
is automatically set to the value of U>.
I
f the value U> (slow overvoltage shutdown) is set to a value which is
smaller than the value of U
con
,
max.
(maximum restart voltage) using the
LC display, then the value of U
con
,
max.
is automatically set to the value of
U>.
I
f the value f< (slow underfrequency shutdown) is set to a value which is
greater than the value of f
con
,
min.
(minimum restart frequency) using the
LC display, then the value of f
con
,
min.
is automatically set to the value of
f<.
I
f the value f> (slow overfrequency shutdown) is set to a value which is
smaller than the value of f
con
,
max.
(maximum restart frequency) using the
LC display, then the value of f
con
,
max.
is automatically set to the value of
f>.
BE CH-NS
CY DE-NS
DK LU-NS
4
1
2
3
4
Frequency shutd.
NOTE: The device continuously monitors the grid frequency. If
the grid voltage exceeds or drops below the configured val-
ues, the device switches off.
1. Set limit values for underfrequency and overfrequency in 0.1 Hz in-
crements.
2. Set period from occurrence of the fault to shutdown of the device.
4
1
2
3
4
Enh. Parameters
F
Further parametrization possible via WEBGUI!
4
1
2
3
4
DC starting volt.
The device begins feed-in as soon as this DC voltage is present.
F
Set the starting voltage.
4
1
2
3
4
DC connection
F
Select between automatic detection and manual setting.
NOTE: Note the connection examples!
4
1
2
3
4
Const. volt. ctrl
NOTE: Option to disable the MPP seek mode in order to oper-
ate the device with a constant DC voltage.
1. Activate or disable the constant voltage controller.
2. Set value for constant voltage controller.
CAUTION! When constant voltage operation and "Q on De-
mand" operation are activated, feedback can occur on the PV
generator. Please observe the instructions and approval of the
module manufacturer.