No. Grid
LED
LED
Display
Status description
Action
Pers
.
37
Unknown hardware
No valid version of the power unit was detec-
ted. Incorrect hardware installed.
Switch DC + AC off -
> Wait 5 min. -> If
the fault is still
present then ar-
range for a service
to take place. The
firmware on the
device does not
support the hard-
ware available. -->
use suitable firm-
ware
B E
38
Error: Generator Voltage too
high Error: Battery over-
voltage
PV overvoltage error The solar voltage of the
generators has exceeded the permissible max-
imum value
Contact a qualified
electrician!
E
41
Grid failure undervoltage L1 Grid failure over/undervoltage Lx grid voltage
Lx below set minimum permissible grid voltage
Check AC voltage at
connection termin-
als. Check set values
in the parameter
menu. Contact the
service department
if the error persists
E
42
Grid failure overvoltage L1
See description in the event of a fault 41
See action in the
event of a fault 41
E
43
Grid failure undervoltage L2 See description in the event of a fault 41
See action in the
event of a fault 41
E
44
Grid failure overvoltage L2
See description in the event of a fault 41
See action in the
event of a fault 41
E
45
Grid failure undervoltage L3 See description in the event of a fault 41
See action in the
event of a fault 41
E
46
Grid failure overvoltage L3
See description in the event of a fault 41
See action in the
event of a fault 41
E
47
Grid failure phase-to-phase
voltage
The phase angle between the individual
phases of the three-phase supply network is
not correct, possibly no three phase connec-
tion
see action in the
event of a error 42
B/K
48
Grid failure underfrequency Grid frequency below the minimum permiss-
ible grid frequency set
Check set values in
the parameter
menu. Fault can be
caused by a poor
connection on the
AC side. Check con-
nection terminals
from the device to
the grid connection.
E
49
Grid failure overfrequency
Grid frequency above the maximum permiss-
ible grid frequency set
see action in the
event of an error 48
E
50
Grid failure: average voltage The grid voltage measurement according to EN
50160 has exceeded the maximum permitted
limit value. This fault may be grid-related.
Contact a qualified
electrician!
E
56
SPI Remote disconnection
Shutdown via digital input Remote control for
Italy CEI 0-21 Remote trip Off
-
-
Manual
Maintenance and troubleshooting | 11
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Page 79
EN