Commissioning
8.1
Requirements
DANGER
Lethal voltages are still present in the connections and cables of the device even after the
device has been switched off and disconnected!
Coming into contact with the lines and/or terminals/busbars in the device can cause serious injury or
death.
›
The device is only permitted to be commissioned by a qualified professional.
›
Unauthorised persons must be kept away from the device.
The device has been mounted and electrically installed.
The PV generator supplies a voltage above the configured start voltage.
1 Connect the grid voltage using the external circuit breakers.
2 Connect the PV generator using the DC isolator switch (0 > 1)
»
The device begins operation.
» During initial start-up: Follow the instructions in the associated application note – Installing and using the app.
NOTE
For initial start-up of the device, the enclosed communication unit must be plugged into the COM3
connection port.
A mobile terminal device with a WIFI interface is required for monitoring and setting parameters. No serial
number dependent password is required here.
The following functions are only available via the associated app:
-
Initial start-up.
-
Setting parameters
-
Special parameters (e.g. P(f), P(U), Q(U))
-
Reset to Factory defaults.
8.2
Preconditions relating to standards
Attachment of safety label in accordance with UTE C15-712-1
The code of practice UTE C15-712-1 requires that, upon connection to the French
low-voltage distribution network, a safety sticker showing a warning to isolate both
power sources when working on the device must be attached to each device
-
Attach the safety sticker provided to the outside of the device housing
where it is clearly visible
.