Action / step sequence
LB
RB
Notifications / function
-
NOTE: Once the USB stick has been re-
moved, the device reboots and features
the updated data.
NOTE: If a button is not pressed within 15 secs:
no valid file found.
Procedure is aborted. USB stick can be re-
moved.
NOTE: Procedure failed.
USB stick can be removed.
Setting the network parameters to the factory defaults using the multi-function buttons
Action / step sequence
LB
RB
Notifications / function
F
Press the left-hand function button (> 5
secs) to commence the procedure.
-
F
Release the function key.
F
Press the right-hand function button (~0.5
secs) to commence the procedure.
Procedure is carried out.
-
Procedure completed. Network settings
have been reset.
NOTE: If a button is not pressed within 15 secs:
Procedure aborted.
Connecting the device to the grid using the multi-function buttons
Action / step sequence
LB
RB
Notifications / function
NOTE: Starts from status "Device discon-
nected"
F
Press the right-hand function button (> 5
secs) to commence the procedure.
-
F
Release the function key.
F
Briefly (< 1 sec) press the right-hand func-
tion button to commence the procedure.
Procedure is carried out.
-
Procedure in progress. Device is con-
nected to the grid.
-
NOTE: Device is on the grid!
NOTE: If a button is not pressed within 15 secs:
Procedure aborted.
Disconnecting the device from the grid using the multi-function buttons
Action / step sequence
LB
RB
Notifications / function
F
Press the right-hand function button (> 5
secs) to commence the procedure.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 69