Attach the DRM 0 safety sticker
According to AS/NZS 4777.2:2015, in Australia PV devices are marked that support
the "Mode 0" remote control command.
F
Attach the supplied sticker next to the name plate on the device housing where it
is clearly visible.
Fig. 42:
Sticker DRM 0 for Australia
8.3
Network topologies
Segmentation of the system
SEGMENT 2
BP1
BP2
BP3
BPk
BPj
Ethernet
Line
Topology
max. 100m
SC
SC
SC
SC
SC
SC
SC
SC
Segment
Controller
2)
SEGMENT 1
BP1
BP2
BP3
BPj
BPm
BPk
Ethernet
Ring
Topology
max. 100m
SC
SC
SC
SC
SC
SC
SC
SC
Segment
Controller
2)
B
P
4
B
P
5
SEGMENT M
BP1
BP2
BP3
BPi
BPk
BPj
Ethernet
Ring
Topology
max. 100m
SC
SC
SC
SC
SC
SC
SC
SC
Segment
Controller
2)
Max. 100m
Network
Segment Switch
(RSTP)
Main network switch
FO Switch
FO Switch
Fiber
Splicebox
Splicebox
Internet
Network
Segment Switch
(RSTP)
Gateway
VPN 3G/4G Router
B
P
4
B
P
5
BPi
B
P
4
B
P
5
max. 100 nodes/segment
typ. 10MW/segment
Legend:
SC: ARGUS
String Combiner
BP: blueplanet 125
Inverter
1): meteocontrol blue’Log XC
2): meteocontrol blue’Log XM
RS485
DC
RSTP: Rapid Spanning Tree
Protocol
MQTT
MODBUS/TCP
FTP
HTTP(S)
MODBUS/RTU
MQTT: Messge Queuing
Telemetry Transport
Plant
Controller
1)
HTTP(S)
Cloud
meteocontrol Portal
WEB-
Server
Database-
Server
App-
Server
XMPP
Service
User
HTTP(S)
1
2
5
3
4
6
7
8
9
10
Fig. 43: Segmentation of a plant
1
Gateway VPN 3G/4G router
6
Network segment switch
2
Main network switch
7
Inverter device
3
FO - switch (fibre optic)
8
String combiner
4
Slicebox (for fibre optic data transfer)
9
Connection cable and protocol
- DC / Modbus RTU / RS485
5
Segment Controller
10
Plant Controller
This illustration shows a possible variant for multiple segments. Depending on the local conditions, a different positioning
of the components may also be preferable (e.g. position
Segment Controlle
r at a central location and connect in
the segment switch via glass fibre cable).
Located directly after the Gateway VPN-Router, is the
main network switch
via which the
segment con-
troller
is connected in. With the corresponding system size (distance from
main network switch
to the
seg-
ment controller
>100 m), it may also be necessary to connect in segments that are further away via a glass fibre
connection.
Within a segment, the KACO devices can be coupled to one another via the integrated switch in an Ethernet daisy chain,
whereby the segment controller is connected to the first element of the chain. This topology is displayed in segment 2, for
example. A
Segment Controller
can manage up to 100 nodes. A node in this sense is any data source that is moni-
tored by the
Segment Controller
. (Example: 45 pairs consisting of inverter and string combiner (90 nodes) + 10 re-
serve nodes for other substation/segment data sources)
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3