Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
P(f) gradient
0 – 200 [%/ Hz]
F
Set gradient of power limit function with increasing frequency in % /
Hz. This percentage relates to the nominal frequency of 50 Hz.
Determines the active power reduction subject to the frequency.
The active power is reduced by a gradient in %-P
ref
. In the event of a fre-
quency deviation of one Hz, the configured reduction of the output
power is carried out. The percentage value relates to P
ref
, the actual
power level at the time the frequency exceeds the configured activation
threshold (PM).
NOTE: A drop in the range of 2 % to 12 % corresponds to a gradient in
the range of 100 %/Hz to 16 %/Hz.
4
1
2
3
4
P(f) gradient in the
case of a decreasing
frequency
0 – 200 [%/ Hz]
F
Specify gradient in the case of a decreasing frequency as a %
0
(per
thousand) / minute (if mode "1" or mode "2" is active).
4
1
2
3
4
P(f) activation thresh-
old
45 Hz – 70 Hz
F
Specify activation threshold (if mode 1 or mode 2 is active, this menu
item is displayed permanently for IT and IL!)
NOTE: The function is activated if the activation threshold is exceeded.
In mode 2 this value also serves as a deactivation threshold.
4
1
2
3
4
P(f) intentional delay
0 – 5000 [ms]
F
Set the power limitation delay in seconds.
Not for IL,
IT
4
1
2
3
4
P(f) deactivation time
0 – 3600 [s]
F
Specify time for power reduction (if mode 1 is active).
4
1
2
3
4
P(f) deactivation gradi-
ent
0 – 60000 [% / min]
F
Determine the deactivation gradient.
4
1
2
3
4
Dynamic gradient
mode
On | Off
F
Activate dynamic gradient.
4
1
2
3
4
P(f) minimum deactiva-
tion frequency
45 – 61.5 [Hz] / &
P(f) maximum deacti-
vation frequency
45 – 70 [Hz]
F
Specify the minimum deactivation frequency in Hz.
NOTE: Only evaluated in mode 1.
The function is deactivated if the frequency returns to the range be-
tween the minimum and maximum deactivation threshold and remains
in this range for the duration of the deactivation time.
4
1
2
3
4
P(f) settling time
200 – 2000 [ms]
Password protection
Status
1 Set the P(f) settling time mode.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Increasing output gra-
dient & Decreasing
output gradient
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Voltage-dependent
NOTE: Activate voltage-dependent power reduction in the P(U) menu.