Saving ambient brightness as brightness threshold 

The ambient brightness can be saved as brightness threshold with the aid of the teach function. 

Do not shadow the motion detector during the measuring process. 

Motion detector is in automatic operation. 

Press 

É

 button. 

Teach function is activated. For confirmation, the switched on light is switched off. If the 
light is switched off, this is switched on for approx. 1 second. 
After 30 seconds, the motion detector measures the brightness and saves it. For 
confirmation, the light is switched on for the duration of the run-on time. 

If a value greater than 200 lux is saved, the motion detector switches to day operation 
independent of the brightness. 

Setting fixed run-on time 

Press 

Ï

Ð

Ñ

 or 

Ò

button. 

Setting individual run-on time 

The individual run-on time can be set within a range of 10 seconds to 60 minutes. One of the 
fixed run-on times can be set again at any time. 

Press 

Ó

 button. 

Run-on time starts. 

When the required run-on time is reached, press 

Ô

 button. 

Motion detector saves the run-on time. 

Switching on short time operation 

Press the 

Î

 button for longer than 10 seconds. 

No run-on time is set in short time operation. 

With the HVAC insert, the function is only executed for 

Kanal 1

 output. 

To switch off short time operation, press 

Reset

 button for less than 10 seconds.a 

Switching on dimming phase 

The motion detector is combined with a dimming insert. 
Dimming phase is switched off. 

Press 

Õ

 button. 

Dimming phase is switched on. If pressed again, the dimming phase is switched off again. 

Switching on night light function 

The motion detector is combined with a dimming insert. 
The light is switched between two brightness values (see chapter 3. Function). 

Press the 

Ö

 button for longer than 10 seconds. 

To switch off the night light function, press 

Reset

 button for less than 10 seconds. 

Configuring the motion detector for use outdoors 

The motion detection is switched accordingly for use outdoors in order to minimise faulty 
switching. 

Press the 

×

 button for longer than 10 seconds. 

The motion detection is optimized for use outdoors. If a motion is detected, the red LED (4) 
flashes.  

To reactivate the motion detection for indoors, press 

Reset

 button for less than 10 

seconds. 

Switch on test operation 

The test operation is used for testing the detection area. 

Press 

Ù

 button. 

7/13 

32576803 
J:0082576803 

03.05.2011 

Light Management  

Universal automatic switch 180° 2.20 m 

Содержание AS 1280-1 Series

Страница 1: ...Device is not suitable for disconnection from supply voltage The load is not electrically isolated from the mains even when the device is switched off Do not press on the sensor window Device can be...

Страница 2: ...imit is reached To avoid any light swings caused by a cooling illuminant the motion detector does not evaluate any motion signals for a brief lockout time after switching off The motion detector adjus...

Страница 3: ...he light is switched on for the run on time after mains return Longer than 2 seconds The motion detector goes through a self test for approx 40 seconds after mains return The light is first switched o...

Страница 4: ...er than 10 seconds Adjusting detection angle Brightness threshold approx 1 lux night operation Brightness threshold approx 10 lux switching takes place during twilight Brightness threshold 150 lux set...

Страница 5: ...switched on output HLK continues switching motion dependent Switching off On for 2 hours or Continuous on o Press button for Continuous on function press alternative button 7 on the motion detector A...

Страница 6: ...tton or 2 wire extension insert over entire surface for longer than 3 seconds Switch on brightness is saved For confirmation the light is switched off briefly and switched on again i In the state as s...

Страница 7: ...an 10 seconds i No run on time is set in short time operation i With the HVAC insert the function is only executed for Kanal 1 output i To switch off short time operation press Reset button for less t...

Страница 8: ...e extension insert Only a few settings are possible in combination with a 3 wire extension insert Setting sensitivity see Chapter Operation on a main unit Use outdoors see Chapter Operation on a main...

Страница 9: ...o Avoid interference sources in the detection area Interference sources such as heaters fans air conditioners and cooling illuminants can lead to unwanted switching Motions crosswise to the motion det...

Страница 10: ...with the frame onto the concealed insert i Do not connect any main units in parallel This can lead to light swings 6 2 Commissioning Insert battery into IR remote control i Keep contacts of batteries...

Страница 11: ...s Installation height 1 10 2 20 m Detection angle 180 cross walking range approx 12 x 6 m walk to walking range approx 8 4 m Short time operation pulse duration approx 0 3 s pulse stop approx 2 7 s I...

Страница 12: ...ity Limit detection area Cause 2 On for 2 hours or Continuous on is activated Switch on automatic mode Cause 3 Night light function is switched on The light stays on at 20 brightness Switch off night...

Страница 13: ...61 89 mail vka jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 mail vkm jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 mail...

Отзывы: