Presence simulation
In automatic operation, the motion detector continuously saves times for which the lighting was
switched on or off. A maximum of 120 switching operations are saved over a period of 7 days. If
more switching operations take place, the oldest ones are overwritten respectively. If the
presence simulation is activated, the motion detector performs the saved switching operations.
If not enough switching operations are saved, random switching operations are performed.
Detected motions prolong the run-on time or the light is switched on depending on brightness.
Times are not saved.
i
A motion detector on a 3-wire extension insert does not save any times.
i
With the HVAC insert, the function is only performed for channel 1.
Night light function
The motion detector is combined with a dimming insert. If the night light function is activated,
the light is switched between two brightness values. In idle state, the brightness is 20 % of the
maximum brightness. If motions are detected, the light is switched to the switch-on brightness.
i
If the Off for 2 hours function or continuous Off function is active, the light is switched off.
Behaviour after a mains failure
-
Less than 0.2 seconds: the old switching position is restored after mains return.
-
0.2 seconds until approx. 2 seconds: The light is switched on for the run-on time after
mains return.
-
Longer than 2 seconds: The motion detector goes through a self-test for approx.
40 seconds after mains return. The light is first switched on. After approx. 10 seconds, the
light is switched off. After the end of the self-test, the light is switched on for the duration of
the run-on time. The motion detector is in automatic operation.
4 Operation on a main unit
Display LED
Behind the lens (8) are a red (4) and a yellow (6) LED (Figure 1) for indicating different
operating states.
Red LED
Yellow LED
Signalling
off
on
Light switched on continuously
on
off
Light switched off continuously
flashed in rhythm of the
detection
off
Detection of motion, for
outdoor use
flashes
off
Receipt of IR signals
off
on for 1 second
IR signal detected
The operation and necessary settings are carried out using the IR remote control. Some
settings are carried out one time during the commissioning and should only be changed if the
ambient conditions change.
i
Switching on and dimming can also be carried out via 2-wire extension inserts. Switching
on is also possible with an installation button.
Function buttons IR remote control
Button
Function
¿
Pressing for less than 0.4 seconds
Continuous on
¿
Pressing for longer than 0.4 seconds Only dimming inserts: Dimming until maximum
brightness
À
Automatic operation
Á
Pressing for less than 0.4 seconds
Continuous off
3/13
32576803
J:0082576803
03.05.2011
Light Management
Universal automatic switch 180° 2.20 m