background image

Presence simulation 

In automatic operation, the motion detector continuously saves times for which the lighting was 
switched on or off. A maximum of 120 switching operations are saved over a period of 7 days. If 
more switching operations take place, the oldest ones are overwritten respectively. If the 
presence simulation is activated, the motion detector performs the saved switching operations. 
If not enough switching operations are saved, random switching operations are performed. 
Detected motions prolong the run-on time or the light is switched on depending on brightness. 
Times are not saved. 

A motion detector on a 3-wire extension insert does not save any times. 

With the HVAC insert, the function is only performed for channel 1. 

Night light function 

The motion detector is combined with a dimming insert. If the night light function is activated, 
the light is switched between two brightness values. In idle state, the brightness is 20 % of the 
maximum brightness. If motions are detected, the light is switched to the switch-on brightness. 

If the Off for 2 hours function or continuous Off function is active, the light is switched off. 

Behaviour after a mains failure 

Less than 0.2 seconds: the old switching position is restored after mains return. 

0.2 seconds until approx. 2 seconds: The light is switched on for the run-on time after 
mains return.  

Longer than 2 seconds: The motion detector goes through a self-test for approx. 
40 seconds after mains return. The light is first switched on. After approx. 10 seconds, the 
light is switched off. After the end of the self-test, the light is switched on for the duration of 
the run-on time. The motion detector is in automatic operation. 

4 Operation on a main unit 

Display LED 

Behind the lens (8) are a red (4) and a yellow (6) LED (Figure 1) for indicating different 
operating states. 

Red LED 

Yellow LED 

Signalling 

off 

on 

Light switched on continuously 

on 

off 

Light switched off continuously 

flashed in rhythm of the 
detection 

off 

Detection of motion, for 
outdoor use 

flashes 

off 

Receipt of IR signals 

off 

on for 1 second 

IR signal detected 

The operation and necessary settings are carried out using the IR remote control. Some 
settings are carried out one time during the commissioning and should only be changed if the 
ambient conditions change. 

Switching on and dimming can also be carried out via 2-wire extension inserts. Switching 
on is also possible with an installation button. 

Function buttons IR remote control 

Button 

Function 

¿

 Pressing for less than 0.4 seconds 

Continuous on 

¿

 Pressing for longer than 0.4 seconds  Only dimming inserts: Dimming until maximum 

brightness 

À

Automatic operation 

Á

 Pressing for less than 0.4 seconds 

Continuous off 

3/13 

32576803 
J:0082576803 

03.05.2011 

Light Management  

Universal automatic switch 180° 2.20 m 

Содержание AS 1280-1 Series

Страница 1: ...Device is not suitable for disconnection from supply voltage The load is not electrically isolated from the mains even when the device is switched off Do not press on the sensor window Device can be...

Страница 2: ...imit is reached To avoid any light swings caused by a cooling illuminant the motion detector does not evaluate any motion signals for a brief lockout time after switching off The motion detector adjus...

Страница 3: ...he light is switched on for the run on time after mains return Longer than 2 seconds The motion detector goes through a self test for approx 40 seconds after mains return The light is first switched o...

Страница 4: ...er than 10 seconds Adjusting detection angle Brightness threshold approx 1 lux night operation Brightness threshold approx 10 lux switching takes place during twilight Brightness threshold 150 lux set...

Страница 5: ...switched on output HLK continues switching motion dependent Switching off On for 2 hours or Continuous on o Press button for Continuous on function press alternative button 7 on the motion detector A...

Страница 6: ...tton or 2 wire extension insert over entire surface for longer than 3 seconds Switch on brightness is saved For confirmation the light is switched off briefly and switched on again i In the state as s...

Страница 7: ...an 10 seconds i No run on time is set in short time operation i With the HVAC insert the function is only executed for Kanal 1 output i To switch off short time operation press Reset button for less t...

Страница 8: ...e extension insert Only a few settings are possible in combination with a 3 wire extension insert Setting sensitivity see Chapter Operation on a main unit Use outdoors see Chapter Operation on a main...

Страница 9: ...o Avoid interference sources in the detection area Interference sources such as heaters fans air conditioners and cooling illuminants can lead to unwanted switching Motions crosswise to the motion det...

Страница 10: ...with the frame onto the concealed insert i Do not connect any main units in parallel This can lead to light swings 6 2 Commissioning Insert battery into IR remote control i Keep contacts of batteries...

Страница 11: ...s Installation height 1 10 2 20 m Detection angle 180 cross walking range approx 12 x 6 m walk to walking range approx 8 4 m Short time operation pulse duration approx 0 3 s pulse stop approx 2 7 s I...

Страница 12: ...ity Limit detection area Cause 2 On for 2 hours or Continuous on is activated Switch on automatic mode Cause 3 Night light function is switched on The light stays on at 20 brightness Switch off night...

Страница 13: ...61 89 mail vka jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 mail vkm jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 mail...