53
9.3 Response of the output signal on leaving the
scaling range
On leaving the scaling range, the output will, up to a defined limit,
produce a proportional signal (as per NAMUR NE43). These limits
are listed in the table below:
9.4 Manual operation of the analog output
The JUMO ecoTRANS Lf 03 can output a constant analog signal,
for test purposes or commissioning,
see also Chapter 10.2 “Manual operation of the relay outputs”,
page 54.
Below scaling range
Within scaling
range
Above scaling range
0.0 mA
0 — 20 mA
20.5 mA
3.8 mA
4 — 20 mA
20.5 mA
0.0 V
0 — 10 V
10.2 V
20.5 mA
20 — 0 mA
0.0 mA
20.5 mA
20 — 4 mA
3.8 mA
10.2 V
10 — 0 V
0.0V
1.8 V
2 — 10V
10.2 V
10.2 V
10 — 2 V
1.8 V
After a supply failure, manual mode is deactivated.