7 Configuration
148
Parameter
Parameter
Selection/settings
Description
Function
Without function
Function is switched off.
Formula
Mathematical links with freely selectable
variables and operators
Differential (a-b)
Differential of variable a and variable b
Ratio (a/b)
Ratio of variable a to variable b
Humidity (a;b)
Calculation of relative humidity
Variable a: Dry-bulb temperature
Variable b: Wet-bulb temperature
Floating average (a;t)
Floating average of variable a (sampling
interval 1 s)
Channel designa-
tion
Mat ...
Use default text or enter other text.
Name (abbreviation) with max. 5 charac-
ters that is used in the visualizations.
Channel descrip-
tion
Math ...
Use default text or enter other text.
Description (designation) with max. 21
characters (e.g. for curve diagram)
Temperature
None
The math result is displayed in the en-
tered unit
Temperature difference
The math result is a temperature differ-
ence and is shown in °C or °F (depend-
ing on the device settings).
Temperature value
The math result is a temperature value
and is shown in °C or °F (depending on
the device settings).
Unit
5 characters (
%
)
Unit in which the math result (analog val-
ue) is displayed.
Start of display
range
-99999 to
0
to +99999
Lower limit of display range for graphical
display
End of display
range
-99999 to
100
to +99999
Upper limit of display range for graphical
display
Decimal places
Number of pre-decimal and decimal places for the numerical display of the math re-
sult
Even if the number of decimal places is fixed, the format is automatically changed
if needed in order to display all digits before the decimal point.
Auto
Automatic
XXXXXp
No decimal place
XXXXpX
One decimal place
XXXpXX
Two decimal places
XXpXXX
Three decimal places
XpXXXX
Four decimal places
Response in case
of a fault
Behavior if the math function does not produce a valid result due to an invalid input
value.
Output error value
The math error value 5.0E+37 is output.
Output replacement value
The replacement value is output.
Replacement val-
ue
-99999 to
0
to +99999
Replacement value for output in the
event of a fault.
Time const. for
average value
(min)
1
to 9999
Time constant in minutes for calculating
the floating average
?
Содержание 706521
Страница 2: ......
Страница 24: ...3 Mounting 24 chapter 11 1 10 Case Page 272...
Страница 36: ...4 Electrical connection 36...
Страница 71: ...71 5 Operation 4 Enter password 5 Confirm process The process can still be aborted here Step Action...
Страница 74: ...5 Operation 74...
Страница 190: ...7 Configuration 190...
Страница 278: ...11 Annex 278...
Страница 279: ......