183
7 Configuration
Device address
For the interface type RS485, the device address of the Modbus may only occur once within a connec-
tion (multiple devices connected to a bus). It is less significant for interface type RS232, as only one de-
vice may be connected to the serial interface.
Timeout monitoring, timeout
This function monitors the communication between the Modbus master and Modbus slave from the per-
spective of the Modbus slave. After enabling timeout monitoring, a timer starts when the first request is
received (the timer time is the time set as the "Timeout"). The timer starts to run again after each new
request. If the request does not appear, an internal digital signal is activated after the timer has elapsed
and an entry is made in the alarm and event list. The signal is reset with the next request.
7.22.2
Modbus master
The device acts as a Modbus master.
Device dialog box
Parameter
Alarm/Event text
Use default text or enter other text.
Text that is displayed in the event of an
alarm and entered in the alarm and event
list.
Timeout
250 to
2000
to 99999 ms
Time period for timeout monitoring.
After this time, a failure of the Modbus
master is identified.
Parameter
Selection/settings
Description
?
Parameter
Selection/settings
Description
Timeout
60 to
200
to 10000 ms
A request sent by the master is defined
as faulty if no answer is received within
this time.
Scanning cycle
60 to
500
to 99999 ms
The Modbus master requests data from
the Modbus slave at these intervals.
Содержание 706521
Страница 2: ......
Страница 24: ...3 Mounting 24 chapter 11 1 10 Case Page 272...
Страница 36: ...4 Electrical connection 36...
Страница 71: ...71 5 Operation 4 Enter password 5 Confirm process The process can still be aborted here Step Action...
Страница 74: ...5 Operation 74...
Страница 190: ...7 Configuration 190...
Страница 278: ...11 Annex 278...
Страница 279: ......