137
7 Configuration
Type; Additional storage
Selection "annual" or "total": the counter/integrator status is temporarily stored at the end of each month,
but not reset to 0. This means that the current status is always available for evaluation with the PCA3000
evaluation software at this point in time.
Time base
"Integrator" function: The current measured value is integrated corresponding to the
selected time base, taking the factor into consideration:
Second
The measured value is divided by 1 and
added up every second.
Minute
The measured value is divided by 60 and
added up every second.
Hour
The measured value is divided by 3600
and added up every second.
Day
The measured value is divided by 86400
and added up every second.
"Operating time" function: The time base specifies the unit in which the operation
time is displayed:
Second
Display in seconds
Minute
Display in minutes
Hour
Display in hours
Day
Display in days
Threshold value
"Integrator" function: Integration only takes place if the current measured value is
greater than the threshold value. The time base and factor are not included in the
threshold comparison.
-999999999 to
0
to +999999999
Threshold value
Reset signal
The reset signal is used to set the counter and integrator statuses to 0 (inde-
pendently of other parameters). The current status is not saved in the process.
This reset signal is available in addition to the reset signal described in the previous
chapter "General settings".
Digital selector
The signal (high active) can be selected
from the list of digital signals.
No selection
No signal selected.
Individual settings Instead of the general settings for the synchronization time, daily start, daily end,
period, and day of the week, it is also possible to use individual settings for each
counter/integrator.
Not activated (no checkmark)
The general settings are used.
Activated (checkmark)
The individual settings are used (for "Pa-
rameter" and "Selection/settings": see
the previous chapter "General settings").
Parameter
Selection/settings
Description
Содержание 706521
Страница 2: ......
Страница 24: ...3 Mounting 24 chapter 11 1 10 Case Page 272...
Страница 36: ...4 Electrical connection 36...
Страница 71: ...71 5 Operation 4 Enter password 5 Confirm process The process can still be aborted here Step Action...
Страница 74: ...5 Operation 74...
Страница 190: ...7 Configuration 190...
Страница 278: ...11 Annex 278...
Страница 279: ......