Technical data
8.2
Connection options
CAUTION
The device may only be installed
by qualified technical personnel.
The power supply unit must be dis-
connected to make the electrical
installation.
The micro leakage protection system can be
extended by one of the following devices or
functions using the leakage protection (LS)
input:
•
JUDO floor sensor (up to 9 pcs)
The floor sensor triggers in the event
of a water accumulation on the ground;
the signal triggers the immediate shut-
off of the water supply in the micro leak-
age protection system.
•
Sleep mode
For use with devices that depend on an
uninterrupted water supply. Short-cir-
cuiting the input, e.g. by a relay contact
or by a simple switch, causes the micro
leakage protection system to stop moni-
toring the set limit values and interrupts
vacation mode if it has been activated.
After opening of the switch or relay con-
tact, the originally set limit value moni-
toring is once again active.
•
Close mode
For use in the immediate closing of the
water supply by an external switch or
relay contact.
Attention!
•
The operation of the leakage protection
input must be set in the menu of the
micro leakage protection system.
INFO_NO_HEADER
In the factory, the operating mode of
the leakage protection system input is
set to connection of one or more floor
sensors.
Connection: see chapter 8.4
Change the type of connected device via
the
M
key:
1.
Press key M.
2.
Select
Setting
using the arrow keys and
confirm with the OK key.
3.
Select
Leakage protection
and confirm.
4.
Select
Leakage protection (LS) input
and confirm.
5.
Select one of the following settings and
confirm.
Input (LS)
• Floor sensor
or
Input (LS)
• Sleep mode
or
Input (LS)
• Close mode
The connection is set to the desired
device type or the desired setup.
32
JUDO JPCS
1703593 • 2022/10