Operation
Starting micro leakage testing manu-
ally
Prerequisite:
all water withdrawal points
must be closed during micro leakage test-
ing.
1.
Press
Menu
key.
2.
Select
Leakage protection
using the
arrow keys and confirm with the OK
key.
Main menue
• Leakage pro-
tect
3.
Select
micro leakage
using the arrow
keys and confirm with the OK key.
Leakage protect
• Micro leakage
testing
Micro leakage testing starts.
If no micro leakage has been
detected,
the display alternates
between
No leakage
occurred
To acknowledge
press <OK>
The display returns to the operating dis-
play.
If no micro leakage has been
detected,
the display alternates
between
Small leakage
occurred
To acknowledge
press <OK>
The display returns to the operating dis-
play.
INFO_NO_HEADER
Micro leakage testing can be
started manually at any time
even when a regular automatic
test had been set.
Prerequisite for automatically
running micro leakage testing is a
period of
at least one hour, in which no
water withdrawal takes place.
4.4
Setting limit values
Exceeding of the set limit values for
•
maximum water quantity
•
maximum water flow
•
maximum water withdrawal time
leads to shutting off of the water supply.
INFO_NO_HEADER
When setting the limit values, con-
sideration must be given to devices
that depend on a sometimes very low
continuous water supply over a long
period of time to ensure their proper
functioning (e.g. certain tumble dry-
ers, etc.).
It is also possible to operate such
devices using sleep mode of the
micro leakage protection system.
1703593 • 2022/10
JUDO JPCS