Installation
1
2
Fig. 4:
Rotary flange fitting
1
Profile flange seal
2
Flow direction arrow
Procedure:
1.
Loosen the two union nuts of the built-
in rotary flange and remove them with
the pipe sockets from the built-in rotary
flange fitting.
2.
Fit the two pipe sockets with union nut
into the pipeline.
3.3
Installation of the device
CAUTION
For proper sealing the profile of
the profile flange seal must point
towards the rotary flange fitting
Fig. 5:
Placing and engaging the device
(fastening principle)
1
Feed screws through
2
Turn clockwise to engage
Fig. 6:
Device connection engaged
(fastening principle)
Initial situation:
•
The rotary flange fitting is installed in
the pipe and still closed with the mount-
ing cover.
Do not undo the screws on the device!
1.
Open the shut-off valve upstream of the
installation location or the stopcock and
flush the pipe with the newly installed
rotary flange fitting by opening a down-
stream withdrawal point.
2.
Close the withdrawal point again and
shut off the water again upstream of the
installation location (stopcock or shut-
off valve).
3.
Remove the mounting cover of the
rotary flange fitting AND the respective
fastening screws.
4.
Insert the heads of the four flange
screws of the device through the bay-
onet holes on the rotary flange fitting
5.
Turn the device in a clockwise direc-
tion as far as it will go (see Figure 5 and
6.
Tighten the four flange screws.
UNIT
Select the tightening torque (about
4 Nm) so that the seal is effective
and the device is not damaged or
strained!
10
JUDO JPCS
1703593 • 2022/10