Field Configurators HARTConf, LHPConf for Transmitters with HART or LHP Communication and HART-USB Modem

HARTConf, LHPConf

Field Configurators and HART-USB Modem

for Transmitters with LHP or HART Communication

3.1 Application

HARTConf and LHPConf handheld configuration devices are 
intended for reading, adjusting and changing the configuration 
of  instruments  with  HART  and  LHP  communication.  These 
devices communicate with instruments connected in a current 
loop  or  they  can  supply  these  instruments  being  adjusted 
directly from their internal current supply unit. Therefore, they 
can  be  used  for  the  adjustment  of  instruments  before  their 
installation,  and  before  putting  them  into  operation  without 
connecting  them  necessarily  to  a  power  supply  unit.  The 
internal  power  supply  unit  for  a  transmitter  can  be  switched 
off, permanently switched on or switched into standby mode, 
when the power supply is switched on only for the moment the 
communication is in progress, and then it is switched off again. 
This mode of operation can significantly extend the operating 
period in case the device is supplied from an accumulator or 
a battery. The configurator and its functions are controlled by 
means of push buttons and a colour graphic display.

3.2 Functions of the HARTConf configurator

The  HARTConf  configurator  is  an  instrument  that  combines 
a handheld device with HART or LHP communication and an 
intelligent HART-USB modem. It enables one to communicate 
with  instruments  equipped  with  HART  communication  at 
the  level  of  universal  and  common  practice  commands. 
Therefore,  it  is  possible  to  change  the  output  range  of  any 
HART  instrument,  display  actual  value  of  input,  output  and 
up  to  three  other  variables.  It  is  possible  to  test  a  current 
loop,  do  a  zero  setting  of  a  pressure  sensor,  change  text 
items  etc.  All  available  configuration  parameters  can  be 
set  in  HART-USB  Modem  mode  with  suitable  PC  software 
(software  is  not  included  with  HARTConf).  It  also  includes 
all  functions  of  a  LHP  configurator,  and  it  can  therefore  be 
used for the adjustment of all parameters of LHP transmitters.  
It is supplied from a 9 V accumulator, which can be charged 
from  a  USB  port.  After  connection  to  the  USB  port,  the 
configurator  is  supplied  through  this  port,  which  provides  all 
necessary energy. The device is able to supply the transmitter 
from its own internal power supply unit both in the configurator 
mode and the HART-USB Modem mode.

3.3 Functions of the LHPConf configurator

It  only  contains  the  LHPConf  configurator  function  and  does 
not support connection to device with HART communication. 
In instruments with LHP communication, the device allows to 
adjust  all  available  parameters  except  for  user  linearization. 
It can visualize momentary input and output values and max. 
three other variables, as well as test an output current loop, etc. 
It contains the function of a transmitter supply, and operation 
with  a  transmitter  therefore  does  not  require  any  external 
power  supply  unit.  LHPConf  configurator  is  supplied  from 
a 9 V battery by default. If the accumulator is used instead of 
battery, it is possible to charge the device by connecting to the 
USB port or AC adapter. After connection to the USB port, the 
configurator  is  supplied  through  this  port,  which  provides  all 
necessary energy.

3.4 Dimensional drawings

3. Product description

• Adjustment of the range of HART and LHP 
  instruments by setting the numerical value 
  or calibration on the input value
• Display of momentary input and output values 
  of connected instrument, and up to three other variables
• Testing a current loop, and zero setting of a sensor
• Changing notes, units, damping, etc.
• Power supply for transmitter without any 
  external power supply unit
• Configurator powering from an accumulator, 
  USB or a prismatic battery
• Up to 15 hours of continuous operation
• Using the instrument as a HART-USB modem
• Language versions CZ, EN, DE, RU or as required

Содержание HARTConf

Страница 1: ...variables Testing a current loop and zero setting of a sensor Changing notes units damping etc Power supply for transmitter without any external power supply unit Configurator powering from an accumulator USB or a prismatic battery Up to 15 hours of continuous operation Using the instrument as a HART USB modem Language versions CZ EN DE RU or as required Accessories NL0899EN 2019 08 JSP s r o Indu...

Страница 2: ...and disposal 3 2 1 End of service 3 2 2 Disposal 3 3 Product description 4 3 1 Application 4 3 2 Functions of the HARTConf configurator 4 3 3 Functions of the LHPConf configurator 4 3 4 Dimensional drawings 4 3 5 Block diagram 5 4 Installation operation and maintenance 6 4 1 Installation and commissioning 6 4 2 Menu 7 4 3 Error messages 10 4 4 Operation and maintenance 11 5 Product specifications ...

Страница 3: ...ng transport 1 5 Storage The products shall be stored at temperatures from 20 C to 40 C and maximum relative humidity 80 in the rooms with elimination of condensation of water vapours on the products The stored products shall not be exposed to any shocks vibrations and effects of harmful vapours and gases 1 6 Installation and commissioning During installation commissioning operation and maintenanc...

Страница 4: ... can be set in HART USB Modem mode with suitable PC software software is not included with HARTConf It also includes all functions of a LHP configurator and it can therefore be used for the adjustment of all parameters of LHP transmitters It is supplied from a 9 V accumulator which can be charged from a USB port After connection to the USB port the configurator is supplied through this port which ...

Страница 5: ...ER HART HART LHP BATTERY Blokové schéma ručního konfigurátoru HARTConf MICROCOMPUTER KEYBOARD LHP DISPLAY POWER MANAGEMENT STEP UP DC POWER DC POWER LHP LHP BATTERY Blokové schéma ručního konfigurátoru LHPConf MICROCOMPUTER USB SERIAL KEYBOARD HART USB DISPLAY POWER MANAGEMENT DC DC DC AC DC POWER HART HART LHP BATTERY Blokové schéma ručního konfigurátoru HARTConf MICROCOMPUTER KEYBOARD LHP DISPLA...

Страница 6: ...sure that Battery Type is set to Accumulator If not set the switch correctly This ensures correct charging when the instrument is connected to USB 4 1 4 Installation of USB driver Correct work with a USB interface and charging through a USB requires the necessary USB driver installed on the PC Usually operating system search for a suitable driver after connecting the configurator to the USB port I...

Страница 7: ... s n Assembly No Units Trim DAC zero Trim DAC gain Device reset Sensor zeroing Polling addr Read Enter value Apply value OK Activate Terminate OK Manufacturer Model Burst mode Software rev Hardware rev Lower limit Upper limit Min span Assembly No Sensor s n Lower RV Upper RV Damping Date Tag Descriptor Message Transfer funct Unit Burst cmd Write protect Alarm signal Status Battery type Number form...

Страница 8: ...OFF Configurator HART Modem OK FW Update by Poll addr by Tag OK Int Ext Battery saver OK Read Enter value OK Editor handling Position change Symbol or number change OK Confirm or reject to save value Error Lower limit Upper limit Min span Message Assembly No Sensor s n Assembly No Units Trim DAC zero Trim DAC gain Device reset Sensor zeroing Polling addr Read Enter value Apply value OK Activate Te...

Страница 9: ...ardware rev Primary var Secondary var Tertiary var Fourth var Output current of range Lower RV Upper RV Damping Sensor input Sensor connect Compensation Date Tag Descriptor Alarm signal Write protect Fixed output Oper mode Disp refresh Number format Firmware Power supply OK OK OK OK OK OK OK Read Enter value Apply value OK Turn OFF OK Int Ext Battery saver OK Read Enter value OK Error Manufacturer...

Страница 10: ... Sensornummer Messanfang Messende Dämpfung Datum TAG Beschreibung Nachricht Übertr funktion Phys Einheiten Burst Befehl Schreibgeschützt Alarmart Status Batterietyp Zahlenformat Prim Batterie Akku OK Normal Erweitert OK Geräterevision Geräterevision Erweit Zustand Burst Sprache Löschen OK Sensornummer Übertr funktion Gerätenummer Long Tag Sensor PV OK Sensor PV Kompens TC Kompensation CVD Wert Ro ...

Страница 11: ...change Symbol or number change OK Confirm or reject to save value Ошибки Нижний предел Верхний предел Мин диапазон Сообщение сборки Серийный сборки Единицы Регулир 4 мА Регулир 20 мА Сброс устройства Обнуление датч Адрес опроса Читать Изменить Примен значен OK Включить Выключить OK Производитель Модель Пакет режим Версия ПО Аппарат верс Нижний предел Верхний предел Мин диапазон сборки Серийный Нач...

Страница 12: ...рвичная Вторичная Третья Четвертая Выходной ток диапазона Начало диапаз Конец диапаз Демпфирование Вход датчика Схема подкл Компенсация Дата Тег Дескриптор Авар сигнал Защита записи Фикс выход Режим работы Обновл дисп Формат номера Версия ПО Питание OK OK OK OK OK OK OK Читать Изменить Примен значен OK Выключить OK Внутр Внеш Энергосбережение OK Читать Изменить OK Ошибки Производитель Модель Идент...

Страница 13: ...he connected instrument does not support this command Service Menu of service functions Warning These functions are intended for advanced users only because they can cause a permanent change in parameters or adversely affect the calibration of the connected instrument Service Fixed Output It carries out output current loop test by the selected current After the current value is set and confirmed t...

Страница 14: ...fic device 4 3 Error messages The configurator saves up to 10 error messages or warnings that were sent to it from the connected instrument Some errors have more possible meanings according to the type of the instrument and desired activity The list of error messages together with the possible explanations Invalid selection incorrect combination of parameters Too large the value is too big Too sma...

Страница 15: ... 65 x 32 mm Material of case Black ABS Weight 85 g without battery Working position Arbitrary HART LHP interface Communication protocol HARTConf HART rev 5 LHP LHPConf LHP Transmitter supply voltage min 12 VSS 22 mA switch on switch off energy saving mode USB interface USB standard USB 1 1 Max power demand from USB interface With transmitter supply 140 mA Without transmitter supply 30 mA Battery c...

Страница 16: ...m and field handheld configurator for transmitters with HART and LHP communication function of transmitter supply supplied from USB or accumulator charged from USB Code Language 1 CZ Czech EN English DE German RU Russian Code Optional accessories only for HARTConf HARTWinConf PC configuration software HARTWinConf CZ EN WIN XP Vista 7 8 10 Example of order LHPConf ED Ex stock version 1 The language...

Страница 17: ...JSP s r o Raisova 547 506 01 Jičín Czech Republic 420 493 760 811 export jsp cz www jsp cz Your Supplier ...

Отзывы: