Field Configurators HARTConf, LHPConf for Transmitters with HART or LHP Communication and HART-USB Modem

4.2.5 Menu control

In the menu you can scroll by using directional pushbuttons; 
the  pushbutton  OK  is  used  for  confirmation  or  entry  to  the 
following level; the left arrow button is used for exit. The right 
arrow button is used for displaying long character chains. 
The HARTConf configurator can work in two operating modes - 
Configurator and HART Modem. The operating mode is chosen 
in the menu „Selection“ in the item „Operating mode“. 
In  the  Configurator  mode,  the  USB  interface  is  used  for 
recharging only. In the HART Modem operating mode, one can 
communicate  with  the  connected  instruments  only  when  the 
USB  interface  is  connected  to  the  PC  by  means  of  suitable 
communication  software  (not  included  in  the  HARTConf 
delivery).

4.2.6 Menu items

Information

A set of parameters identifying the connected instrument.

Variables

Reading  and  showing  momentary  values  of  max.  four  input 
quantities  (measured  or  calculated),  output  current,  and 
percentage of the range. By pressing the OK button during the 
display, the size of the figure displayed is doubled.

Configuration

Menu for changing parameters of connected instrument.

* Configuration | Lower RV | Enter Value
* Configuration | Upper RV | Enter Value

This  selection  enable  to  change  a  preset  range  by  entering 
a value. The value editor makes it possible to enter any positive 
or negative number. The up and down arrows keys set a number 
value or the decimal point position. The right or left arrows keys 
change the momentary set position. One can leave the editor 
mode just by pressing the OK push button. A set value is stored 
only when confirmed by the user. A change in the range is not 
carried out when it is outside the maximum range limits, when 
the instrument is in the setting protection mode, or when the 
connected instrument does not support this command.

* Configuration | Lower RV | Apply Value 
* Configuration | Upper RV | Apply Value

This selection enables one to set the beginning or end of the 
range to the momentary input value. When the input quantity is 
connected to the input of the instrument and stabilised, carry 
out the „Apply Value“ command and acknowledge the assuring 
question. A change in the range is not carried out when it is 
outside the maximum range limits, when the instrument is in 
the setting protection mode, or when the connected instrument 
does not support this command.

Service

Menu of service functions.

Warning! 

These  functions  are  intended  for  advanced 

users  only  because  they  can  cause  a  permanent 
change in parameters or adversely affect the calibration 

of the connected instrument.

* Service | Fixed Output

It carries out output current loop test by the selected current. 
After  the  current  value  is  set  and  confirmed,  the  output  of 
connected instrument is adjusted to the required value. 

Caution! 

A control loop, as the case may be, must be 

switched to manual operation in advance!

* Service | Sensor Zeroing

It carries out a sensor zero trimming to the momentary input 
value. This adjustment is used particularly in differential pressure 
sensors after their installation. This zero setting eliminates an 
error caused by the sensor position, static pressure, etc. The 
zero setting is not performed in case the input value is outside 
maximum limits for zero setting, the instrument is in the setting 
protection mode or when the connected instrument does not 
support this command.

Caution!

  The  zero  setting  of  an  absolute  pressure 

sensor  can  result  in  permanent  damage  to  the 
instrument adjustment!

* Service | Trim DAC Zero
* Service | Trim DAC Gain

The configurator trims the start and gain of the D/A converter 
for the conversion of the digital value of the output current to 
real  output  current.  Accurate  performance  of  this  operation 
requires  measuring  the  output  current  with  at  least  0.01% 
accuracy.

* Service | Polling Addr.

To each HART instrument is assigned an address within the 
0  -  15  range. The  standard  factory  setting  is  0.  Addresses  1 
–  15  are  used  in  the  Multi-Drop  mode,  which  results  in  the 
output current setting at 4 mA. After a change in address, one 
must adjust the mode of connection initialisation in the menu 
Options | Initialization. 

* Service | Device reset

It  shall  RESET  the  processor  of  the  connected  instrument. 
Execution of this command does not change any configuration 
parameter, and temporary functions are cancelled. In principle, 
it  is  equivalent  to  the  disconnection  of  supply  voltage  of  the 
connected instrument with its subsequent reconnection.

* Service | Device test

It  shall  carry  out  a  software  test  of  the  instrument. The  test 
result  is  available  in  the  form  of  error  reports.  In  case  no 
error reports show up, the test has identified no defects. The 
configurator does not provide more detailed results of the test.

* Service | Burst

This  command  switches  on  a  burst  mode.  In  this  mode,  the 
instrument continuously sends out a command set in “Service 
| Burst Cmd” without being asked to. In the burst mode, one 

Содержание HARTConf

Страница 1: ...variables Testing a current loop and zero setting of a sensor Changing notes units damping etc Power supply for transmitter without any external power supply unit Configurator powering from an accumulator USB or a prismatic battery Up to 15 hours of continuous operation Using the instrument as a HART USB modem Language versions CZ EN DE RU or as required Accessories NL0899EN 2019 08 JSP s r o Indu...

Страница 2: ...and disposal 3 2 1 End of service 3 2 2 Disposal 3 3 Product description 4 3 1 Application 4 3 2 Functions of the HARTConf configurator 4 3 3 Functions of the LHPConf configurator 4 3 4 Dimensional drawings 4 3 5 Block diagram 5 4 Installation operation and maintenance 6 4 1 Installation and commissioning 6 4 2 Menu 7 4 3 Error messages 10 4 4 Operation and maintenance 11 5 Product specifications ...

Страница 3: ...ng transport 1 5 Storage The products shall be stored at temperatures from 20 C to 40 C and maximum relative humidity 80 in the rooms with elimination of condensation of water vapours on the products The stored products shall not be exposed to any shocks vibrations and effects of harmful vapours and gases 1 6 Installation and commissioning During installation commissioning operation and maintenanc...

Страница 4: ... can be set in HART USB Modem mode with suitable PC software software is not included with HARTConf It also includes all functions of a LHP configurator and it can therefore be used for the adjustment of all parameters of LHP transmitters It is supplied from a 9 V accumulator which can be charged from a USB port After connection to the USB port the configurator is supplied through this port which ...

Страница 5: ...ER HART HART LHP BATTERY Blokové schéma ručního konfigurátoru HARTConf MICROCOMPUTER KEYBOARD LHP DISPLAY POWER MANAGEMENT STEP UP DC POWER DC POWER LHP LHP BATTERY Blokové schéma ručního konfigurátoru LHPConf MICROCOMPUTER USB SERIAL KEYBOARD HART USB DISPLAY POWER MANAGEMENT DC DC DC AC DC POWER HART HART LHP BATTERY Blokové schéma ručního konfigurátoru HARTConf MICROCOMPUTER KEYBOARD LHP DISPLA...

Страница 6: ...sure that Battery Type is set to Accumulator If not set the switch correctly This ensures correct charging when the instrument is connected to USB 4 1 4 Installation of USB driver Correct work with a USB interface and charging through a USB requires the necessary USB driver installed on the PC Usually operating system search for a suitable driver after connecting the configurator to the USB port I...

Страница 7: ... s n Assembly No Units Trim DAC zero Trim DAC gain Device reset Sensor zeroing Polling addr Read Enter value Apply value OK Activate Terminate OK Manufacturer Model Burst mode Software rev Hardware rev Lower limit Upper limit Min span Assembly No Sensor s n Lower RV Upper RV Damping Date Tag Descriptor Message Transfer funct Unit Burst cmd Write protect Alarm signal Status Battery type Number form...

Страница 8: ...OFF Configurator HART Modem OK FW Update by Poll addr by Tag OK Int Ext Battery saver OK Read Enter value OK Editor handling Position change Symbol or number change OK Confirm or reject to save value Error Lower limit Upper limit Min span Message Assembly No Sensor s n Assembly No Units Trim DAC zero Trim DAC gain Device reset Sensor zeroing Polling addr Read Enter value Apply value OK Activate Te...

Страница 9: ...ardware rev Primary var Secondary var Tertiary var Fourth var Output current of range Lower RV Upper RV Damping Sensor input Sensor connect Compensation Date Tag Descriptor Alarm signal Write protect Fixed output Oper mode Disp refresh Number format Firmware Power supply OK OK OK OK OK OK OK Read Enter value Apply value OK Turn OFF OK Int Ext Battery saver OK Read Enter value OK Error Manufacturer...

Страница 10: ... Sensornummer Messanfang Messende Dämpfung Datum TAG Beschreibung Nachricht Übertr funktion Phys Einheiten Burst Befehl Schreibgeschützt Alarmart Status Batterietyp Zahlenformat Prim Batterie Akku OK Normal Erweitert OK Geräterevision Geräterevision Erweit Zustand Burst Sprache Löschen OK Sensornummer Übertr funktion Gerätenummer Long Tag Sensor PV OK Sensor PV Kompens TC Kompensation CVD Wert Ro ...

Страница 11: ...change Symbol or number change OK Confirm or reject to save value Ошибки Нижний предел Верхний предел Мин диапазон Сообщение сборки Серийный сборки Единицы Регулир 4 мА Регулир 20 мА Сброс устройства Обнуление датч Адрес опроса Читать Изменить Примен значен OK Включить Выключить OK Производитель Модель Пакет режим Версия ПО Аппарат верс Нижний предел Верхний предел Мин диапазон сборки Серийный Нач...

Страница 12: ...рвичная Вторичная Третья Четвертая Выходной ток диапазона Начало диапаз Конец диапаз Демпфирование Вход датчика Схема подкл Компенсация Дата Тег Дескриптор Авар сигнал Защита записи Фикс выход Режим работы Обновл дисп Формат номера Версия ПО Питание OK OK OK OK OK OK OK Читать Изменить Примен значен OK Выключить OK Внутр Внеш Энергосбережение OK Читать Изменить OK Ошибки Производитель Модель Идент...

Страница 13: ...he connected instrument does not support this command Service Menu of service functions Warning These functions are intended for advanced users only because they can cause a permanent change in parameters or adversely affect the calibration of the connected instrument Service Fixed Output It carries out output current loop test by the selected current After the current value is set and confirmed t...

Страница 14: ...fic device 4 3 Error messages The configurator saves up to 10 error messages or warnings that were sent to it from the connected instrument Some errors have more possible meanings according to the type of the instrument and desired activity The list of error messages together with the possible explanations Invalid selection incorrect combination of parameters Too large the value is too big Too sma...

Страница 15: ... 65 x 32 mm Material of case Black ABS Weight 85 g without battery Working position Arbitrary HART LHP interface Communication protocol HARTConf HART rev 5 LHP LHPConf LHP Transmitter supply voltage min 12 VSS 22 mA switch on switch off energy saving mode USB interface USB standard USB 1 1 Max power demand from USB interface With transmitter supply 140 mA Without transmitter supply 30 mA Battery c...

Страница 16: ...m and field handheld configurator for transmitters with HART and LHP communication function of transmitter supply supplied from USB or accumulator charged from USB Code Language 1 CZ Czech EN English DE German RU Russian Code Optional accessories only for HARTConf HARTWinConf PC configuration software HARTWinConf CZ EN WIN XP Vista 7 8 10 Example of order LHPConf ED Ex stock version 1 The language...

Страница 17: ...JSP s r o Raisova 547 506 01 Jičín Czech Republic 420 493 760 811 export jsp cz www jsp cz Your Supplier ...

Отзывы: