Figure 7.  Clearance to a combustible shelf.

Flue System Installation

Flue outlet (spigot) dimensions: 

Internally = 8 mm 

Externally = approx. 3 mm

When installing the vent, it is important to adhere to 

national and local regulations that apply. Only one appli-

ance may be connected to the vent system.

The vent system must terminate above the roof.
The vent system and the flue pipe components must 

be fastened to the stove with screws.

Minimum height of the chimney is approx. ,5 m (7’) 

and maximum height should not be more than approx. 

0,7 m (35’). (When installation is at or above a height of 

approx. 60 m (000’), the chimney’s height must be at 

least approx. 3,7 m (’.) measured from the flue outlet. If 

the chimney has to move through a horizontal distance, 

make sure to use 45º or 90 º bends.

Max. number of 45º bends = 4
Max. number of 90º bends = 3
It is permitted to move the chimney a total of approx. 

, m (4’) horizontally.

An exhaust hood (terminal, cowl or rain cap) must be 

mounted at the chimney’s termination point . After fit-

ting of the vent system and installation of the appliance, 

carry out a smoke test on the flue as described in the 

relevant section.  If the appliance shuts off in operation 

for no apparent reason (especially during windy or stormy 

conditions) and will not relight, it is possible that the flue 

system safety switch has operated. Allow the appliance 

to cool down and relight. Any obstruction to the flow of 

exhaust gases up the flue can cause this switch to operate 

thereby making the situation safe. If the appliance cuts 

out repeatedly, do not continue to use the appliance and 

seek flue checking and service from qualified personnel 

before re-using the appliance.

Closure Plate Installation

It is permissible to install this appliance using a closure 

plate installation similar to traditional outset gas fires. 

See diagrams ( E-F) on page 8. The British Standards de-

tailing this type of installation are BS587 pt and BS5440 

pt . The appliance and flue must be sound and if used 

with solid fuel or oil appliances it must be swept prior to 

installation. There must be no other openings other than 

the exit from the top of the flue and the opening into 

which the appliance is being installed. All cracks, holes, 

underfloor air vents etc must be removed and sealed fully 

before installation continues. A proprietary metal flue box 

complying with BS75 is a suitable appliance opening.

Figure 8.   Vent height requirements.

Figure 9.   Closure plate and flue requirements.

�������

�����

��

�������

�����

�����������

���������������

�����������

����������������

����������������

����

�����

����

������

�����

������

��������������������������

�����������������

Closure Plate

600 mm

Содержание GF 400 CF

Страница 1: ...DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas sup plier from a neighbor s phone Follow the g...

Страница 2: ...n Company Date Service details Annual service year 5 Sign Company Date Service details Annual service year 6 Sign Company Date Service details Annual service year 7 Sign Company Date Service details A...

Страница 3: ...aller Information 6 5 User Information 12 6 Troubleshooting 14 THIS OWNER S MANUAL PROVIDES INFORMATION TO ENSURE SAFE INSTALLATION AND EFFICIENT DEPENDABLE OPERATION OF YOUR STOVE PLEASE READ THESE I...

Страница 4: ...p Flue Nett 77 9 78 2 Efficiency Class 2 2 NOx Class 4 5 Main Burner Injector Marking 33 51 Pilot Injector Marking 51 30 Notes The appliance is supplied at the default factory settings for Natural Gas...

Страница 5: ...intended for use on a gas installation with a governed gas supply Safety Precautions This appliance must be installed in accordance with the rules in force Consult instructions before installation and...

Страница 6: ...all not be put out of operation by the installer When the TTB is exchanged only original manufacturer s parts shall be used Installation Guide for Qualified Personnel Important The appliance is factor...

Страница 7: ...he appliance shuts off in operation for no apparent reason especially during windy or stormy conditions and will not relight it is possible that the flue system safety switch has operated Allow the ap...

Страница 8: ...ppliance and connect to the gas supply and carry out a smoke test on the flue as described in the relevant section of this manual Assembly Prior To Installation The product is delivered in 1 package I...

Страница 9: ...e embers realistically simulate glowing coals when the burner is operating These should be spread evenly over the burner plate and around the logs 1 Engage the holes in the underside 0f the Right Log...

Страница 10: ...awn into the flue and no smoke should spill into the room If the smoke does issue into the room leave for another 5 minutes and retest The appliance is fitted with a TTB flue sensing safety switch If...

Страница 11: ...this dimension is preset at the factory For Propane 18 5 mm must be set by installer CAUTION To avoid burns do not adjust the air shutter until the burner has cooled down Figure 22 Safety switch loca...

Страница 12: ...vide extra protection Operating Instructions Lighting Note Odors when using the stove When used for the first time the appliance may emit an irritating gas that may smell a little The gas is not toxic...

Страница 13: ...sing the stove for the first time Adjusting the Heat Setting Heat and flame size can be adjusted by turning the regu lator knob C marked HI LOW which is located next to the gas control knob see fig 23...

Страница 14: ...and when the valve is being replaced Troubleshooting When No Spark is Generated at the Pilot Head It is uncommon for the Piezo spark ignitor fig 25 A to fail unless it has mechanical damage If the spa...

Страница 15: ...for at least 30 seconds Make sure the flame is centred at the thermo couple Make sure the thermocouple is enveloped by the flame up to at least 3 mm 1 8 from the tip fig 20 If the flame is abnormally...

Страница 16: ...at there are 2 threaded holes fig 16 B and C that can be used when installing a new thermocouple Make sure the blue wire A is fastened at the same threaded hole The nut on the thermocouple must not be...

Страница 17: ...ral Gas Open 21 5 mm Warning To avoid burns do not adjust the air open ing until the burner has cooled down Blocked orifice Make sure the main orifice fig 28 is dirt free and that the orifice has the...

Страница 18: ...18 ONLY USE REPLACEMENT PARTS PROVIDED BY AN AU THORIZED J TUL DEALER Figure 29 J tul GF 400 CF Illustrated Parts Breakdown...

Страница 19: ...220641 Burner Orifice LP 1 70 mm 045027 38 Air Shutter 220790 39 Gasket 2 25 OD 118023 40 Wing Nut M6 117975 41 Washer 2 25 OD 220734 42 Screw 8 x 3 4 117986 43 Pilot Assembly NG 129471 44 Spacer Pil...

Страница 20: ...nformance with local and national building regulations Before beginning the installation it is important that the these instructions be carefully read and understood J tul maintains a policy of contin...

Отзывы: